Panel operation – Access levels 1 and 2  

 

1 Normal condition  

Under normal conditions and in Manual & Auto mode, the unit will have only the green, Power On LED lit. With the ENABLE 
controls key switch off, LCD will show:  

Manual & Auto  

When switched to Manual Only mode, the Manual only yellow LED will be lit and the display will show:  

MANUAL MODE  

The ECU has 3 access levels. Access level 1 is available at all times and allows operation the Buzzer silence button and the Lamp 
test function by holding down the EXIT button for more than 2 seconds. Access level 2 is enabled after operation of the front 
panel mounted Enable Controls key switch and Access level 3 allows configuration options to be set following operation of the 
Write Enable switch while at access level 2 (Enable Controls keyswitch operated).  

 

2 Access level 2  

With the Enable Control key switch operated, the LCD will display:  

Access level 2 

  

ENTER for Menu  

Press the ENTER button to view the following menu options.  
 

2.1 Disable Extinguishant release outputs.  

To disable both of the Extinguishant release outputs, press the UP button on the module while at access level 2.  
The display will show:  

DISABLE  

EXTING. RELEASE ? 

Press the Enter button to select this function. The display will show:  

ENABLE  

EXTING. RELEASE ? 

The yellow disabled LED on the module that has been disabled will be lit.  

Turn the Enable key switch off to leave the disablement active. To re-enable the Extinguishant outputs repeat the procedure 
above.  
 

2.2 Disable Manual release  

To disable all Manual release inputs (front panel mounted and remotely connected), press the UP button on the module while at 
access level 2 until the module displays:  

DISABLE  

MANUAL RELEASE ? 

Press the Enter button to select this function. The display will show:  

ENABLE  
MANUAL RELEASE ? 

The yellow disabled LED on the module that has been disabled will be lit.  

Turn the Enable key switch off to leave the disablement active. To re-enable the manual release facility repeat the procedure 
above.  
 

2.3 Disable Stage 1 output  

To disable the 1

st 

Stage relay output, press the UP button on the module while at access level 2 until the display shows:  

DISABLE  

stage 1 output ? 

Press the Enter button to select this function. The display will show:  

ENABLE  
STAGE 1 OUTPUT ? 

The yellow disabled LED on the module that has been disabled will be lit.  

Turn the Enable keyswitch off to leave the disablement active. To re-enable the Stage 1 relay output repeat the procedure 
above. 

2.4 Disable Stage 2 output  

To disable the 2

nd 

Stage relay output, press the UP button on the module while at access level 2 until the display shows:  

DISABLE  
stage 2 output ? 

Press the Enter button to select this function. The display will show:  

ENABLE  
STAGE 2 OUTPUT ? 

The yellow disabled LED on the module that has been disabled will be lit.  

Turn the Enable keyswitch off to leave the disablement active. To re-enable the Stage 2 relay output repeat the procedure 
above.  
 

2.5 Disable Released output  

To disable the Released relay output, press the UP button on the module while at access level 2 until the display shows:  

DISABLE  
released output ? 

Press the Enter button to select this function. The display will show:  

ENABLE  
released OUTPUT ? 

The yellow disabled LED on the module that has been disabled will be lit.  

Turn the Enable keyswitch off to leave the disablement active. To re-enable the Released relay output repeat the procedure 
above.  
 

 