Cabling
Grounding Conductor
Install ground conductors with 14 AWG cabling to support branch
circuits of the Sigma A-CP Fire Control Panel.
Branch Circuits
Protect branch circuits from the AC power source with a 15 Amp fuse.
Material
All field wiring should be installed using fire rated cables according to
the NFPA except AC and TELCO.
Cross Sectional Size
The cross sectional size of zone cabling should be determined based on
length and the number of devices in use. Connect zone cabling using a
minimum of 1 mm cross sectional area.
Operating Environment
Low Temperature
32
o
F ( 0
o
C )
High Temperature
102
o
F ( + 49
o
C )
Relative Humidity
This device functions in an atmosphere of relative humidity up to
93 percent, non-condensing.
Physical Specifications
Cabinet-Box Dimensions
H 12.0” (304.8 mm) X W 14.5” (368.3 mm) X D 3.81” (97.0 mm)
Depth of cabinet-box + Lid = 4.25 “ (108.0 mm)
Mounting
Maximum screw diameter: 0.2" (5 mm) screws
This fire control panel is designed for indoor use only.