Single Zone Fire Condition
Alarm In Zone LEDs flash at 2Hz and the Fire LED lights when fire conditions report through activation
of zone detectors or pull stations. Fire relays operate and trigger connected systems and circuits
during single zone fire conditions.
Silence/Resound Fire Drill
The Silence/Resound Fire Drill button can only be operated in Access Level 2 by turning the Enable
Access key to the right. To silence the NACs, insert the Enable Access key, turn to the right and press
the Silence/Sound alarm button.
When the NACs have been silenced, the Alarm In Zone LEDs will change from flashing to a steady
state. Pressing the Silence/Sound alarm while the fire control panel is in this silenced condition will
cause the NACs to operate again. The NACs can be toggled on and off with the Silence/Sound alarm
button as required.
Reset
The reset command restores operation of the Sigma A-CP Fire Control Panel from an alarm or trouble
condition.
Zone Trouble
Removal of a detector from its base or a trouble on any of the zone wiring will cause the Trouble LED
and Zone Trouble LEDs to flash, indicating the zone in which the trouble has occurred.
NAC Trouble
A trouble on the wiring to sounder circuits will cause the Trouble and NAC Trouble LEDs to flash,
indicating a trouble on the wiring to the sounder circuits.
Power Trouble
Loss of power from the AC source, power supply or standby batteries will cause the Trouble and
Power Trouble LEDs to light.
System Trouble
The System Trouble LED will light if the configuration memory has not been set or has become
corrupted.