6 – Fastmig™ Kms 400 mVU / 0647
© Kemppi oy
60º
max. 15º
2. INSTALLATION
2.1. SITING ThE mAChINE
Site the machine on a stationary, horizontal, dry base in a position that does NOT allow
dust, dirt or metal particles to enter the machines cooling air flow.
2.2. CONNECTION TO ThE mAINS SuPPLy
FastMig™ power sources are delivered equipped with 5 m mains cable without plug.
If local electricity regulations of operating country are stating otherwise, the mains cable should
be replaced in conformity with the local regulations.
Connection of the mains cable, mounting and change of the plug should only be carried out by a
competent electrician.
Remove the machine’s right side plate to enable the mounting of a mains cable.
KMS 400 MVU power source can be connected to the mains supply of 230 V 3~ or 400 V 3~.
Power source recognizes the mains voltage automatically. For fuse and cable sizes, see the technical
data in the end of this document.
If changing the mains cable take into consideration the following:
The cable is entered into the machine through the inlet ring on the rear panel of the machine and
fastened with a cable clamp (05). The phase conductors of the cable are coupled to connectors L1,
L2 and L3. The earth protection coloured green-yellow is coupled to connector.
If you are using 5-lead cable, do not connect neutral conductor.
rain water
– Preferably site the machine somewhat higher above
the floor level.
– Ensure that the front as well as the rear of the
machine there is at least 20 cm free distance to
allow good circulation of the cooling air through
the machine.
– Protect the machine against heavy rain and in hot
circumstances against direct sunshine. Ensure the
free circulation of the cooling air.
Degree of protection of machine IP23S allows at
its maximum the water spray coming in 60º angle
to hit machine’s outer covering.
See to that the machine is positioned away from the line
of particle spray, created by grinding tools etc.