Example A design requirements: ∆p = 50 hPa, V = 200 l/h
Example B design requirements: evaluation via kv-value
(Flow at ∆p = 1000 hPa): 0,85 m³/h = 850 l/h
Example for the setting of the Regulating Valve
4
1
2
3
Pre-Setting read from the graph (here
VE 4.0)
Pre-Setting read from the graph (here
VE 4.0)
Adjust the pre-setting by turning the
handle till scale shows required value.
All intermediate values are
continuously adjustable.
Fixation of pre-setting:
Hold the handwheel and fixate the
control position by turning the
adjustment cap to the limit stop.
After pre-setting the Multi-Fix Plus, the
valve can be used to isolate the pipe
and re-opened not further than the
pre-set value.
A
A
B
B
pre-setting value
Ziffer auf dem Einstellrad
Number on the dial
Cijfer op de indicator
Druckdifferenz/pressure loss/ Drukverschil [hP
a]
10 /20 – K41001506G001-00 /
02.2022 –
©