23
Owner’s manual
EN
provide power to the external devices to ensure power supply continuity. If solar
panels energy is not sufficient or not available, external devices will be supplied with
power only from the battery.
PV priority mode (photovoltaic supply priority):
1. During the day (with ample sunlight) and power supply mains is available: solar
panels will provide power to loads, simultaneously charging the battery (power
supply mains at standby).
2. During the evening (or when the sunshine is not available), when the power supply
mains is available: system will provide power to loads from battery; discharge
battery until battery reaches low voltage protection level; then automatically enter
AC power mode and charge the battery till set value (reserved a certain power in
case of emergency situation, but will not charge the battery fully). The battery will be
fully charged by solar panels once the solar energy is recovered.
TURNING OFF STEPS
1. Turn off the loads one by one.
2. Press and hold the on/off button for about 3 seconds, the loads will be cut off.
3. Disconnect the AC power supply mains.
4. Set the solar switch to OFF.
5. Disconnect from the battery, if the device will not be used for a long time.
SPECIFICATION
Model
URZ3416 - 800 VA
URZ3417 - 1000 VA
URZ3419 - 2500 VA
Power
500 W
700 W
1800 W
Battery voltage
12 VDC
24 VDC
Working mode
PV (Photovoltaic priority) / AC (AC priority)
PV
Input voltage range
15 VDC – 50 VDC
15 VDC – 75 VDC
30 VDC - 100 VDC
Max. charge current
20 A (in regard to connected photovoltaic cell)
40 A (in regard
to connected
photovoltaic cell)
Max. conversion efficiency
98 %
AC
Input voltage range
190 - 260 V
Input frequency range
45-65 Hz
Output voltage range
218 - 241 V
Input PF (AC/DC)
98%
Efficiency
mains mode ≥ 96%
Charge current
10 A