Kelly SPM Mini Full Bridge 4Q Permanent Magnet Motor Controller User
’s Manual
V1.1
14
a temporary over-current, momentarily high or low
battery voltage. This can happen during normal
operation.
3,3
¤¤¤ ¤¤¤
Hall throttle is open
or short-circuit
When the throttle is repaired, a restart will clear the
fault.
3,4
¤¤¤ ¤¤¤¤ Non-zero throttle on
direction change
Controller won‟t allow a direction change unless the
throttle or speed is at zero. Fault clears when throttle
is released.
4,1
¤¤¤¤ ¤
Regen or Start-up
over-voltage
Motor drive is disabled if an over-voltage is detected
at start-up or during regen. The voltage threshold
detection level is set during configuration. The max
threshold is about 1.25 times of controller rated
voltage. I.e. you may set threshold lower than 60V for
48V controller.
4, 3
¤¤¤¤ ¤¤¤
Motor
over-temperature
Motor temperature has exceeded the configured
maximum. The controller will shut down until the
motor temperature cools down.
The Red LED flashes once at power on as a confidence check and then normally stays
Off. “1, 2” means the Red flashes once and after a second pause, flashes twice. The time
between two flashes is 0.5 second. The pause time between multiple flash code groups is
two seconds.