Kelly Jaguar series KLS-N Sinusoidal Brushless PM Motor Controller User

’s Manual 

   

 

  V2.9 

                                                                                                                                         

 

25

 

(6)Brake Rls Time: Brake Release Time, the time of Brake Torque from max to 0, accuracy 0.1s. 
Range: 1~250 
Factory set is 1 
 
(7)BRK_SW Brk %: BRK_SW Braking Percent, the percent of BRK_SW in max braking. Range: 
0~50 
The brake switch regen mode. You have to turn on the brake switch after the throttle is released 
for the regen to occur. 
Factory set is 10 
 
(8)BRK_AD Brk%:It is used to adjust the max regen percentage of brake variable regen mode. 
This regen mode doesn't need brake switch to support any more for KLS controller. 
 
(9)Torque Speed KP: Speed Percent Kp in Torque Mode. Range: 0~10000    Factory set is 3000 
Torque Speed KI: Speed Integral Ki in Torque Mode. Range: 0~500      Factory set is 80 
Speed Err Limit: Speed Error Limit in Torque Mode. Range: 50~4000 Factory set is 1000 
These three parameters are used for PID adjustment. 
If  you  think  the  acceleration  performance  is  very  very  strong,  please  adjust  them  to  a  lower 
value respectively. 
 
(10)Change Dir brake: Value range: Enable and Disable 
It is only useful when you Enable the joystick function. 
If you want to get swift direction changing by using joystick function, you may enable Change 
Dir brake item in user program. 
It will help the motor change the direction of motor quickly after you shift throttle from 0V to 5V,or 
from 5V to 0V. 
Suggestion: factory default is Disable. 
 
(11) 

Compensation Per% 

Tried to increase the current usage during Anti-Slip operation. 
 
(12)IVT BRK MAX and IVT BRK MIN: These two items are only useful when Joystick function is 
enabled in the user program. When you want to use Change Dir Brake to reduce the delay time 
when you shift the direction under joystick operation, there is a RPM limitation to use Change 
Dir Brake function which is only activated when the motor RPM is between IVT BRK MIN and 
IVT BRK MAX. 
Suggestion: factory default is Disable. 
 

(13)Torque Speed Kp:3000  

Torque Speed Ki:80 

Speed Err Limit:1000 

Содержание KLS7240ND

Страница 1: ...around Sinusoidal Brushless PM Motor Controllers User s Manual Devices Supported KLS2412ND KLS4812ND KLS7212ND KLS8430ND KLS2412N KLS4812N KLS7212N KLS8430N KLS2418ND KLS4818ND KLS7215ND KLS2418N KLS...

Страница 2: ...Features 4 2 3 Specifications 5 2 4 Name Regulation 5 Chapter 3 Wiring and Installation 6 3 1 Mounting the Controller 6 3 2 Connections 13 3 3 Installation Check List 17 Chapter 4 Programmable Paramet...

Страница 3: ...It uses high power MOSFET s and SVPWM and FOC to achieve efficiencies of up to 99 in most cases A powerful microprocessor brings in comprehensive and precise control to the controllers It also allows...

Страница 4: ...hall sensors 10 5 switch inputs which are activated by connection to 12V Default to throttle switch brake switch reversing switch forward switch and Boost switch 11 3 analog 0 5V inputs that default t...

Страница 5: ...current cutback warning and shutdown at configurable high and low battery voltage 13 Aluminum based PCB board with heat sink plate on the bottom of controller 14 Waterproof connectors for small signa...

Страница 6: ...al Full Power Operating Temperature Range 0 to 70 MOSFET temperature Operating Temperature Range 40 to 100 MOSFET temperature Max Battery Current Configurable 2 4 Name Regulation The name regulation o...

Страница 7: ...S7218ND 48 72V 36 86V 240A Up to 130A KLS7218N 48 72V 36 86V 240A 80A 120A KLS7230ND 48 72V 36 86V 280A Up to 150A KLS7230N 48 72V 36 86V 280A 90A 135A KLS7240ND 48 72V 36 86V 320A Up to 160A KLS7240N...

Страница 8: ...ller User s Manual V2 9 7 Figure 1 KLS2412ND KLS4812ND KLS7212ND KLS7215ND mounting holes dimensions dimensions in millimeters B B U V W M5 Bolts Figure 2 KLS2412N KLS4812N KLS7212N KLS7215N mounting...

Страница 9: ...y Jaguar series KLS N Sinusoidal Brushless PM Motor Controller User s Manual V2 9 8 Figure 3 KLS2418ND KLS2430ND KLS4818ND KLS4830ND KLS7218ND KLS7222ND mounting holes dimensions dimensions in millime...

Страница 10: ...elly Jaguar series KLS N Sinusoidal Brushless PM Motor Controller User s Manual V2 9 9 Figure 4 KLS2418N KLS2430N KLS4818N KLS4830N KLS7218N KLS7222N mounting holes dimensions dimensions in millimeter...

Страница 11: ...Kelly Jaguar series KLS N Sinusoidal Brushless PM Motor Controller User s Manual V2 9 10 Figure 5 KLS7230ND KLS7240ND KLS8430ND mounting holes dimensions dimensions in millimeters...

Страница 12: ...Kelly Jaguar series KLS N Sinusoidal Brushless PM Motor Controller User s Manual V2 9 11 Figure 6 KLS7230N KLS8430N mounting holes dimensions dimensions in millimeters...

Страница 13: ...Kelly Jaguar series KLS N Sinusoidal Brushless PM Motor Controller User s Manual V2 9 12 Figure 7 KLS7240N mounting holes dimensions dimensions in millimeters...

Страница 14: ...4 CAN bus is not included in KLS N controller by default When boost is disabled in user program pin2 is used as brake analog regen mode When boost is enable pin2 is used for boost function You may not...

Страница 15: ...Hall B Hall phase B Dark Green 16 Hall C Hall phase C Dark Blue Notes 1 All RTN pins are internally connected 2 Meter function is to copy either of hall sensors 3 Switch to 12V is active Open switch...

Страница 16: ...f KLS N Controller Figure 11 KLS N controller standard wiring Battery voltage can be used for controller supply 3 2 3 Optional wiring of KLS N controller The 12V input signal of the pin supplies the s...

Страница 17: ...ng diagram for motor temperature sensor NOTE KLS controller can support KTY84 130 150 and KTY83 122 thermistors 3 2 4 Communication Port A 4pin connector to RS232 port is provided to communicate with...

Страница 18: ...e checkout Make sure the PWR switch and the brake is off Use well insulated tools Make sure the wire is connected correctly Turn the PWR switch on The fault code will be detected automatically at rest...

Страница 19: ...n7 to batteries for Identification Angle operation Please download the instruction how to use Identification angle function from our website www kellycontroller com support php 4 1 Step 1 1 Low Volt T...

Страница 20: ...ly again Then everything will be fine The motor is ready to be drived by the KLS controller Range 85 or 170 nothing else 6 TPS Low Err Hall active pedal if lower than the value report the fault of TPS...

Страница 21: ...gh Range 60 95 Functional description Set throttle effective ending point Suggestion Set according to the practical situation factory default is 80 5V 4 0V 14 Max output Fre Max output frequency Unit...

Страница 22: ...ctive output the controller will report fault and not operate Suggestion Set according to the practical situation factory default is Disable 21 NTL H Pedal Neutral position High Pedal Disable Only use...

Страница 23: ...oot switch is turned off Please see figure 4 1 Suggestion Set according to the practical situation factory default is Disable Configuration Pin Status Running Status Forward Switch Foot Switch FWD_SW...

Страница 24: ...elp the motor stop on the downhill But usually this function only helps motor stop rolling back too fast Suggestion factory default is Disable 28 Change Direction If the direction is not what you expe...

Страница 25: ...less for KLS N or KLS M model 4 3 Step 3 1 RLS_TPS Brk RLS TPS Braking Percent the percent of Releasing Pedal BRK in max braking Range 0 50 This is used to adjust the regen current of releasing thrott...

Страница 26: ...for PID adjustment If you think the acceleration performance is very very strong please adjust them to a lower value respectively 10 Change Dir brake Value range Enable and Disable It is only useful w...

Страница 27: ...is normal This item is only useful for internal calculation for MCU 246 is about 11 degrees in environment 4 4 How to use Identification angle operation function We must do Identification angle opera...

Страница 28: ...Kelly Jaguar series KLS N Sinusoidal Brushless PM Motor Controller User s Manual V2 9 27 2 Please connect the controller to user program by using an USB to RS232 cable and SM 4A DB9 RS232 Converter...

Страница 29: ...B to RS232 cable and SM 4A DB9 RS232 Converter to connect the controller to an Android Tablet The third option is customers can buy our Bluetooth converter to connect the controller to Android Phone W...

Страница 30: ...g Because the 85 means this controller finished the identification angle operation with the motor in factory before shipment Your motor is different from the motor from controller supplier 5 Please fi...

Страница 31: ...codes such as Identify error hall err etc please return to the first picture of user program Please write 85 instead in identification angle by manual If there are no any error codes you can not writ...

Страница 32: ...e the connections to the bus bars if fitted are tight To avoid physically stressing the bus bars use two well insulated wrenches 5 2 Configuration You can configure the controller with a host computer...

Страница 33: ...n for motor and hall sensors in the user program Table 1 Error Codes Buzzer Error Codes Code Explanation Solution 1 1 Automatic error identification 1 Wrong wiring of motor phase line or hall Please s...

Страница 34: ...t condition like a temporary over current momentarily high or low battery voltage This can happen during normal operation 3 3 Hall throttle is open or short circuit When the throttle is repaired a res...

Страница 35: ...PM Motor Controller User s Manual V2 9 34 Contact Us Kelly Controls Home Page http www KellyController com Download user manual instructions and user program www kellycontroller com support php E mail...

Отзывы: