Kelly KLS-H Sinusoidal Brushless Permanent Magnet Motor Controller User
’s Manual
V 1.2
17
Suggestion: Set according to the practical situation. By default, it is set at 20V.
(2)Over Volt: The max voltage of reporting this fault - Range 20~115 depending on different
models
Controller will not operate when battery voltage is higher than the value so as to protect battery
and controller.
Suggestion: Set according to the practical situation.
Please check section 2.4.
(3)Current Percent: Phase Current Percent. Range: 20~100
Functional description: The max motor current is (The Value * Peak Current of the Controller).
Suggestion: Factory default is 100%.
(4)Battery Limit: Battery Limit Current, Limit the max value of Battery Current. Range: 20~100
Functional description: Set max battery current so as to protect battery. A lower value means a
lower battery output current and better protective effect. But excessively low value will affect
acceleration.
Suggestion: Factory default is 100%.
(5)Identification Angle: Please download the instruction to how to use Identification angle
function from the website.
www.kellycontroller.com/support.php
If you can read 85 in Identification Angle item, that is to say, the system is stable and normal.
Please fill in 170 for Identification Angle item in user program. Then
please click Write button in user program. Please wait a few seconds before restart the power
supply. You will see some info on Monitor screen after power supply is
reset. If you see Reset error on the Monitor screen, that is to say, the auto_Identification is
finished. You can see 85 in the Identification Angle item again. And the controller will
blink error code. This is normal. Please reset the power supply again. Then everything will be
fine. The motor is ready to be drived by the KLS controller.
Range: 85 or 170, nothing else.
(6)TPS Low Err: Hall active pedal, if lower than the value, report the fault of TPS Type. Range:
0~20
(7)TPS High Err: Hall active pedal, if higher than the value, report the fault of TPS Type. Range:
80~100
As you may know, the output of hall throttle from Kelly is about from 0.86V to 4.2V.
Our controller will report 3.3 error code if the output of hall throttle is below 0.5V or above 4.5V
by default.
The controller will think the hall throttle is shorted or damaged if the output is beyond the range
from 0.5V to 4.5V.
You can adjust the threshold voltage below or above 0.5V.The controller will report the 3.3 code
to protect the system according to different types of hall throttle.
Because there are many different hall throttle suppliers in the world. The initial output can not be