![Keller Acculevel Скачать руководство пользователя страница 12](http://html.mh-extra.com/html/keller/acculevel/acculevel_user-manual_662263012.webp)
Keller America Inc
User’s Guide
Rev. 07/19
Keller America Inc
User’s Guide
Rev. 07/19
A-9
MINIMUM PIPE BEND RADIUS
Acculevel/ Levelgage
Ø 0.83”
Microlevel
Ø 0.63”
Schedule 40
1” IPS
(Ø1.315 x 0.133”w)
22”
18”
1.5” IPS
(Ø1.900” x 0.145” w)
4”
5”
2” IPS
(Ø2.375 x 0.154”w)
3”
3”
Schedule 80
1” IPS
(Ø1.315 x 0.179”w)
22”
22”
1.5” IPS
(Ø1.315 x 0.200”w)
4”
6”
2” IPS
(Ø2.375 x 0.218”w)
4”
4”
NOTES:
1: FOR LIGHTNING/SURGE PROTECTION TO BE EFFECTIVE, CONNECT
DRAIN WIRE TO A LOW-IMPEDANCE EARTH GROUND.
2: DO NOT SUBMERSE ELECTRICAL TERMINATION IN LIQUID. IT WILL DAMAGE
THE INSTRUMENT.
MICROLEVEL & NANOLEVEL w/ATTACHED CABLE...
4-20mA + RS485
DRAIN (NOTE 1)
BLACK: + SUPPLY
WHITE: OUTPUT/GROUND
BLUE: RS485A
YELLOW: RS485B
DRAIN (NOTE 1)
BLACK: GROUND
WHITE: SDI-12
RED: + VCC
BLUE: RS485A
YELLOW: RS485B
ACCULEVEL SDI w/ATTACHED CABLE...SDI-12+ RS485
A-8