The KLT13I, KLT23I , KLT33I and KLT43I series are electronic 
temperature controllers for cold refrigeration units. 
These devices allow to control the Compressor, Defrost, Fan, 
Alarm and Light,  and have up to 3 probes. The KLT43I series 
includes the possibility of two compressors.
NTC or PTC probes can be selected by parameter. They have 
also a configurable digital input according to parameter E0
These thermostats allow  the Master/Slave configuration to 
synchronize the defrost between different thermostats. 
Errors and alarms can be viewed on display.
HACCP option can record temperature, time of temperature 
alarms and power fails.
The Slink multifunction input allows an easy programming of the 
parameters with a KLKEY, the connection of a Real Time Clock 
and Memory Module or the connection of a R485 Module 
Interface.

Model references

The model reference is given by: KLTX3IB -DVYZ
Each suffix can take the following values:

B

Buzzer:

B:Internal buzzer, Null:Without buzzer

V

Color:

R:Red, G:Green, B:Blue

Y

Supply Voltage:

230:230Vac, 115:115Vac 
24:24Vac/dc, 12:12Vac/dc

Z

Temp. Units:

C:ºC, F:ºF

Installation

Wiring

Avoid installing the cables of the probes and the digital input, in 
the proximity of any power cable. If the length of the probe cables 
measure is longer than 100 meters, a re-calibration adjustment 
must be made  P1 ,  P2    P3

Maintenance

The thermostat must be located in a place protected from 
vibrations, impacts, water and corrosive gases.
It  will be made a 71x29mm panel cut-out to insert  the 
thermostat (apply silicone to make it leaktight ). Then the fixing 
clips must be fasten, sliding it onto the thermostat,  until  it is well 
secure.  

ó

Cleaning 

Clean the surface of the controller with a soft, damp  cloth.  
Never use abrasive detergents, petrol, alcohol or solvents.

Repairs

All the repairs must be carried out by authorised people.

Technical Data

Storage temperature

-20ºC to 80ºC  (

-

4 to 176ºF)

Operating temperature

0ºC to 65ºC (32 to 149ºF)

Temperature probe

PTC / NTC 

Probe range

           

PTC    -50ºC to 150ºC (-58 to 302ºF) 

 

           

NTC    -50ºC to 110ºC (-58 to 230ºF) 

Temperature accuracy

Better than 1

Temperature resolution

    

Supply voltages

/-10%, /-10%
12Vac/dc +/-10%, 24Vac/dc +/-10%

Supply powers

3.6VA (230V)   1.5VA (12V) 

% of full scale

0.1º PTC ,  1º NTC 

Displays

3-digit and sign 

SLINK

       

For KLKEY or Real Time Clock and Memory Module    

       or Communication Module

Outputs

KLT43 Model

REL 1  

SPDT Relé Carga Resistiva 16A
1HP 240Vac -- 10FLA, 60LRA  240Vac

REL 4  

SPDT Relé Carga Resistiva 16A
1HP 240Vac -- 10FLA, 60LRA  240Vac 

    

REL 2  

SPST Relé Carga Resistiva 8A 240Vac  

    

REL 3  

SPDT Relé Carga Resistiva 8A 240Vac  

   

KLT13,KLT23,KLT33 Models

REL 1

SPST Relé Carga Resistiva 16A
1HP 240Vac -- 10FLA, 60LRA  240Vac 

REL 2

SPST relay resistive load 5A 240Vac  

REL 3

SPST Relé Carga Resistiva 8A 240Vac  

Dimensions

77

 

x 36 x 62 mm (3.03 x 1.42 x 2.44 in)

Front Protection

IP64

Parameter description   -   continuation

Defrosting 
d0 = Cold / Heat mode (KLT13)                            

re = Cold

In = Heat

d0 = Type of defrosting (KLT23, KLT33, KLT43)                            

re = defrosting without connecting the compressor.   
in = defrosting by connecting the compressor.          

d1 = End of defrosting temperature.   

When this temperature is reached the defrosting will end.

d2 = Maximum defrosting time.

The defrosting will stop when this time is reached.
If it is zero there will be no defrosting.

d3 = first Hour defrosting of the day

From 00:00 hours the first defrosting is at d3 hours.
Until this time no defrosting is performed

d4 = Delay first defrosting. 

Time to carry out the first defrosting if d3 = yes.

d5 = Display during the defrosting. 

Off = The current temperature will be shown during defrosting.
On = The temperature at defrost beginning is frozen on display 
until the end of defrosting and until the current temperature is   
equal or lower than the initial one, or until d6 time elapses.
-d- = Label -d- is displayed during defrosting, until the end of 
defrosting and until the current temperature is equal or lower than 
the initial one, or until d6 time elapses.

d6 = Display return limit.

Maximum time before viewing   the current temperature again 
after defrosting.

d7 = Compressor drip time.

Time since defrosting ends until the compressor can be 
connected.

d8 = Interval between defrosting. 

Time between the start of a defrosting and the start of the 
following one.
If it is zero defrosting is not done automatically by time.

d9 = Fan operation during defrosting time.

It determines if the fan is connected or not during defrosting.

d10 = Fan drip time.

Time since defrosting ends until fan can be connected.

d11 = Minimum Time duration defrosting

Once defrosting begins it stays at least during this time

d12 = Fan & defrosting control probe.

sd1 = ambient probe.
sd2 = defrosting probe
sd3 = product probe 

d14 = Units to count the defrosting cyle.

rt =   according to the time of working of the controller.
ct = according to the time of working of the compressor.

PROBES 
P0 = ºC or ºF,   Temperature scale
P1 = Ambient probe calibration

Degrees shift of   the ambient probe.

P2 = 

Degrees shift of   the defrosting probe.

P3 = Product

Degrees shift of   the product probe.

P4 = Decimal point
P5=Probe to be viewed normally on the display.

sd1 = ambient probe.
sd2 = defrosting probe.
sd3 = product probe   

P6 = Probe 2   Defrosting   present. 

If there is a probe 2 connected to thermostat

P7 = Probe 3   Product   present. 

If there is a probe 3 connected to thermostat

(DEF)

(Pro)

Defrosting   probe calibration

   probe calibration

ALARMS(ALA)

INITIALIZATION (INI)

A0 = Fan & alarm   differential.

This is the temperature difference between the on and off cycle of 
the alarms and fan

A1 = Maximum   alarm.

High alarm ON at Set+A1. High alarm OFF at Set+A1-A0.

A2 = Minimum   alarm.

Low alarm ON at Set-A2. Low alarm OFF at Set-A2+A0.

A3 = Time validation open door or external alarm.

If open door or external alarm is maintained during this time, alarm 
will be indicated. (Depending on the E0 configuration of digital input)

A4 = Alarm   exclusion time after defrosting.

During the defrosting and this time after it, temperature alarms will 
be ignored.

A5 = Alarm   exclusion   time after opening the door.

While the door is open (if A5>0) and time A5 after closing it, alarms 
will be ignored.

A6 = Alarm   exclusion after connection.

Until this time has elapsed since the connection, temperature 
alarms will be ignored.

A7 = Temperature alarm   time validation.

Time since the alarm situation occurs, until it is given.

A8 = Probe   Alarm. 

   

sd1 = ambient probe
sd2 = defrosting probe
sd3 = product probe 

Hor = Hour 
Min = Minutes
E0 = Digital input configuration.

         Off = Digital input disabled.
         Al   = External alarm. There is an alarm if input is short-circuited.
         In     = Door open if input is short-circuited.
         def = Order to initiate a defrost if input is short-circuited.
         ndf = No defrosting will be made if input is short-circuited.

H0 = Factory   Configuration. 

Record Factory Configuration. 

H1 = Master/Slave

H1=Master. The thermostat issues defrosting orders to slave 
connected thermostats through the digital input
H1=Slave. The thermostat performs defrosting ordered by the 
master connected to its digital input.
In both cases the input must be E0=def

H2 = Keyboard   protection.

Yes =Keyboard protected. To modify Set, activate/de-activate 
defrosting and activate/de-activate continuous cycle we have to 
enter the code and then quit. The protection is removed 
momentarily. It is activated again 1 minute after the last key is 
pressed.
No = Keyboard not protected.

H3 = Delay time on connecting.

Until this time has elapsed since turning-on power, the compressor 
will not start-up.

H4 = Address for serial communication.

H4 from 1 to 255 Modbus protocol, others KELD protocol

H5 = Input code   to parameters.
 

This code is set to 00 from factory.

H6 = Type of Probe 

PTC or NTC

H7 = Configuration 2 Relay and H8 = Configuration Relay 3 

We can choose that it is Light (Li), Fan (Fan), Alarm (ALA) or 
Defrosting (dEF), reverse fan (FAI) 

H9 = Configuration Relay 4 (Single KLT43)

We can choose that it is Light (Li), Fan (Fan), Alarm (ALA), 
Defrosting (dEF) or second compressor (Con)

HdE =

 Hours(HdE):Minutes(MdE) the defrost will begin at

MdE =

 Hours(HdE):Minutes(MdE) the defrost will begin at 

Specification and Operating Instructions

KLTX3

Temperature Controllers

Wiring Diagram

E L E C T R Ó N I C A

E L E C T R Ó N I C A

ETDT1412I_120126

 Electrónica Keld, S.L. 
 Pol.Ind. Empresarium. C/Lentisco 15
 50720 - La Cartuja Baja, ZARAGOZA
 Spain

Phone: +34 976 429 099 

Fax:+34 976 593 532 

E-mail: [email protected] 

Web: http://www.keld.es 

ETDT1412I_120126

 Electrónica Keld, S.L. 
 Pol.Ind. Empresarium. C/Lentisco 15
 50720 - La Cartuja Baja, ZARAGOZA
 Spain

Phone: +34 976 429 099 

Fax:+34 976 593 532 

E-mail: [email protected] 

Web: http://www.keld.es 

1

4

3

2

6

9

7

10

5

Rel1

230Vac

amb.

Com

def.

in.

S

L

IN

K

pro.

KLT13 

1

4

3

2

6

7

5

230Vac

sd1 sd2

in

S

L

IN

K

sd3

Rel3

Rel1

8 9

10 11 12 13 14 15

Rel4

Rel2

16 17 18

KLT43

19

gnd

gnd

1

4

3

2

6

9

8

7

10

5

Rel1

230Vac

Rel2

amb.

Com

def.

in.

S

L

IN

K

pro.

KLT23

1

4

3

2

6

9

8

7

10

5

Rel1

230Vac

Rel2

amb.

Com

def.

Rel3

11

in.

S

L

IN

K

pro.

KLT33