Description

NTC/PTC probe and ºC / ºF scale can be set by the parameters.
The control features defrost synchronization among several thermostats, 
intelligent defrost to reduce the power consumption, control for two 
compressors, night set, error indication and alarms through the display and 
the buzzer, communication and real-time clock.
It also features HACCP logging to record temperature and time of alarms 
caused by out of limit temperatures or power fails.
SLINK multipurpose input allows to connect a KLKEY to easily program the 
parameters or a communication module.

Model references

Installation

The thermostat must be located in a place protected from vibrations, 
impacts, water and corrosive gasses.

Wiring

Avoid installing the cables of the probes and the digital input in the 
proximity of any power cables. 

Maintenance

After the installation there are no maintenance tasks required.
Clean the surface of the controller with a soft, damp cloth.

EKT8 series controllers have been specifically designed for refrigeration 
applications. Friendly use thanks to the display with symbols and 8 keys to 
make it easy to program the parameters and access to functions such as 
turning on/off the control, the light or forcing defrost.
Models up to 5 relays are available. First relay drives the compressor and 
the other four can be configured to drive defrost, fan, light or alarm. It also 
includes 3 temperature probe inputs and 2 configurable digital input.

The model reference is given by: EKT8V DW XYZ
Each suffix can take the following values:

V

Model

depending on table

D

Probe

PTC/NTC selectable by parameter

W

Terminals

T:

Screw  

F

:Fast-on

X

Loads

L:

2 Wires

  C: 

Direct

Y

Color

R

:Red, 

G

:Green, 

B

:Blue

Z

Supply voltage

90255:

115-230Vac  

12

:12Vac/dc

Panel cut-out:

Use the gasket or apply silicone to make it leaktight. Fix the thermostat with 
the supplied screws. Put the screw covers. 

 

Never use abrasive detergents, petrol, alcohol or solvents.
All the repairs must be carried out by authorised people.

 

EKT8

Digital Temperature Controller

Wiring Diagram

ETDT1515I_101203

ETDT1515I_101203

Technical Data

Storage temperature

from -20ºC to 80ºC  (from 

-

4ºF to 176ºF)

Operating temperature

from 0ºC to 55ºC (from 32ºF to 131ºF)

Temperature probe

PTC / NTC 

Probe range

PTC from -50ºC to 150ºC (from -58 to 302ºF) 
NTC from -50ºC to 110ºC (-58 to 230ºF) 

Accuracy

Better than 1% of full scale

Front Operation

Set Point Setup

-  Press key 

Set

   The Set label appears.

- Press 

Set

 again.   Current set point value appears blinking.

- Press 

or

 o increase or decrease the value.

- Press 

Set

 to confirm the new value.

- Press 

Set

 and      to exit

Supply voltage

90-255

 

Vac 50/60Hz

Supply powers

3VA  

Resolution

0.1º

Display

3-digits plus sign

SLINK

For KLKEY and Communication

Outputs

OUT1

Model 1HP  SPST Relay Resistive Load 16A

1HP 240Vac -- 10FLA, 60LRA 240Vac

Model 2HP  SPST Relay Resistive Load 20A

2HP 240Vac -- 12FLA, 72LRA 240Vac

OUT2

SPDT Relay Resistive Load 8A 240Vac

OUT3

SPST Relay Resistive Load 8A 240Vac

OUT4
OUT5

SPDT Relay Resistive Load 16A
1HP 240Vac -- 10FLA, 60LRA 240Vac

Maximum current per position

20A

Dimensions

184

 

x 39 x 64 mm (7.24  x 1.53 x 2.52 in)

Front Protection

Ip65

  

   

 

Parameter description - Continuation

d12 = Fan & defrosting control probe

sd1 = ambient probe.
sd2 = defrosting probe
sd3 = product probe 

d13 = Intelligent defrosting

off =   disabled
Jup = skip defrosts
Cic = vary defrosting cycle

d14 = Units to count the defrosting cycle

rt =   according to the time of working of the controller.
ct = according to the time of working of the compressor.

d15= minimum evaporator set

If evaporator temperature is above d15 the time for defrosting cycle is not 
counted. Only enabled if d3 is not set to off.

d16= maximum defrost time %

Percentage of d2 set as normal defrosting time.

d17= Cycle time variation

Value of   increment or decrement of d8

Hde = 

Hour(Hde):Minutes(Mde) of next defrost

Mde =

Hour(Hde):Minutes(Mde) of next defrost

if 

d14=ct or d13 different of oFF 

Hde:Mde is the time   until   next defrost

JdF= Smart defrost information

d13= jup

 

Defrosts to skip

d13= CiC

 

increment of d8

PROBES 

P0 = ºC or ºF,   Temperature scale
P1 = Ambient probe calibration

Degrees shift of   the ambient probe.

P2 = 

Degrees shift of   the defrosting probe.

P3 = Product

Degrees shift of   the product probe.

P4 = Decimal point
P5=Probe to be viewed normally on the display.

sd1 = ambient probe.
sd2 = defrosting probe.
sd3 = product probe   

P6 = Probe 2   Defrosting   present. 

If there is a probe 2 connected to thermostat

P7 = Probe 3   Product   present. 

If there is a probe 3 connected to thermostat

A0 = Fan & alarm   differential.

This is the temperature difference between the on and off cycle of the 
alarms and fan

A1 = Maximum   alarm.

High alarm ON at Set+A1. High alarm OFF at Set+A1-A0.

A2 = Minimum   alarm.

Low alarm ON at Set-A2. Low alarm OFF at Set-A2+A0.

A3 = Digital Input alarm time validation.

If E0=In or E0=Al, time since the situation occurs, until it is given.

A4 = Temperature alarm exclusion time after defrosting.

During the defrosting, and this time after it, temperature alarms will be 
ignored.

A5 = Temperature alarm exclusion   time after opening the door.

 While the door is open (if A5>0) and time A5 after closing it, alarms will be 
ignored.

A6 = Temperature alarm exclusion after connection.

 Until this time has elapsed since the connection, temperature alarms will 
be ignored.

A7 = Temperature alarm   time validation.

 Time since the alarm situation occurs, until it is given.

A8 = Probe   Alarm. 

   

sd1 = ambient probe
sd2 = defrosting probe
sd3 = product probe

(Pro)

Defrosting   probe calibration

   probe calibration

ALARMS(ALA)

INITIALIZATION (INI)

Hor = Hour 
Min = Minutes
E0, E1 = Digital input configuration.

Off = Digital input disabled.
Al   = External alarm. There is an alarm if input is short-circuited.
In     = Door open if input is short-circuited.
def = Order to initiate a defrost if input is short-circuited (only E0).
ndf = No defrosting will be made if input is short-circuited.
rst= If input is short-circuited Set Point becomes Set+r4

H0 = Factory   Configuration. 

Record Factory Configuration. 

H1 = Master/Slave

H1=Master. The thermostat issues defrosting orders to slave connected 
thermostats through the digital input
H1=Slave. The thermostat performs defrosting ordered by the master 
connected to its digital input.
In both cases the input must be E0=def

H2 = Keyboard   protection.

Yes =Keyboard protected. To modify Set, activate/de-activate defrosting and 
activate/de-activate continuous cycle we have to enter the code and then 
quit. The protection is removed momentarily. It is activated again 1 minute 
after the last key is pressed.
No = Keyboard not protected.

H3 = Delay time on connecting.

Until this time has elapsed since turning-on power, the compressor will not 
start-up.

H4 = Address for serial communication.
H5 = Input code   to parameters.
 

This code is set to 00 from factory.

H6 = Type of Probe 

PTC or NTC

H7 = Configuration Relay 2 , H8 = Configuration Relay 3
H9 = Configuration Relay 4 and H10 = Configuration Relay 5

We can choose that it is Light (Lit), Fan (Fan), Alarm (ALA), Defrosting 
(dEF) or 2nd compressor (Con (Only H9)).

H11 = HACCP

Enables   temperature alarm recording.

dat = Date 

Day, month, year

td = Display refresh time 

If the measures temperature increases over 1 degree in this time, displayed 
temperature only will be increased 1 degree

Model Table

OUT5

OUT3

N L

OUT2

In2

In1

Sd1

1 2 3

6 7 8 9 10 11 12

15

16 17 18 19 20

4 5

OUT4

13 14

21 22

OUT1

INPUTS

SUPPLY

INTERNAL
BUZZER

S. LINK

Sd2

Sd3

OUT5

OUT3

N L

OUT2

In2

In1

Sd1

1 2 3

6 7 8 9 10 11 12

15

16 17 18 19 20

4 5

OUT4

13 14

21 22

OUT1

INPUTS

SUPPLY

INTERNAL
BUZZER

S. LINK

Sd2

Sd3

C

o

m

p

re

s

s

o

r

R

e

la

y

1

6

A

=

1

H

P

2

0

A

=

2

H

P

S

e

c

o

n

d

R

e

la

y

8

A

T

h

ir

d

R

e

la

y

8

A

F

o

u

rt

h

R

e

la

y

1

6

A

F

if

th

R

e

la

y

1

6

A

H

e

a

t

o

r

C

o

o

li

n

g

C

o

n

tr

o

l

S

m

a

rt

D

e

fr

o

s

ti

n

g

B

u

z

z

e

r

R

e

a

l

T

im

e

C

lo

c

k

EKT823

16A

*

*

EKT823B

16A

*

*

*

EKT823BR

16A

*

*

*

*

EKT823H

20A

*

*

EKT823HB

20A

*

*

*

EKT823HBR

20A

*

*

*

*

EKT833

16A

*

*

*

EKT833B

16A

*

*

*

*

EKT833BR

16A

*

*

*

*

*

EKT833H

20A

*

*

*

EKT833HB

20A

*

*

*

*

EKT833HBR

20A

*

*

*

*

*

EKT843

16A

*

*

*

*

EKT843B

16A

*

*

*

*

*

EKT843BR

16A

*

*

*

*

*

*

EKT843H

20A

*

*

*

*

EKT843HB

20A

*

*

*

*

*

EKT843HBR

20A

*

*

*

*

*

*

EKT853

16A

*

*

*

*

*

EKT853B

16A

*

*

*

*

*

*

EKT853BR

16A

*

*

*

*

*

*

*

EKT853H

20A

*

*

*

*

*

EKT853HB

20A

*

*

*

*

*

*

EKT853HBR

20A

*

*

*

*

*

*

*

DIRECT LOADS

2 WIRE LOADS

E L E C T R O N I C A

E L E C T R O N I C A

 Electrónica Keld, S.L. 
 Pol.Ind. Empresarium. C/Lentisco 15
 50720 - La Cartuja Baja, ZARAGOZA
 Spain

Phone: +34 976 429 099 

Fax:+34 976 593 532 

E-mail: [email protected] 

Web: http://www.keld.es 

 Electrónica Keld, S.L. 

Phone: +34 976 429 099 

 Pol.Ind. Empresarium. C/Lentisco 15

Fax:+34 976 593 532 

 50720 - La Cartuja Baja, ZARAGOZA

E-mail: [email protected] 

 Spain

Web: http://www.keld.es

MAX.

20A

Specification and Operating Instructions

165mm

 

165mm

 

150mm

150mm

3

1

m

m

3

1

m

m

m

3m

m

3m

Отзывы: