KELCO E30 Скачать руководство пользователя страница 12

10

Mode 1 Start Pressure 

The start pressure can be set to any value from 1 kPa to 2000 kPa or from 1 psi 

to 290 psi in increments of 1 kPa or 1 psi.  Normally the start pressure would be 

set to the pressure at which you want the pump to start.  In normal operation each 

time pressure drops to whatever value you have set, the pump will start.  Once 

running the pressure can fall to below the value you have set and the pump will 

continue to run. In fact if you have not set the trip pressure to some value greater 

than zero, the pump will continue to run in spite of a complete lack of pressure. 

The start pressure can be set as low as 1 kPa or 1 psi and the E30 will function in 

the manner described above.  If you choose to set the start pressure to zero you 

will invoke a warning message from the E30 to check your pressure settings. The 

E30 will not tolerate having its start pressure set to zero.  The start pressure  must 

always be set to a higher pressure than the trip pressure.  If you have set the trip 

pressure to zero and you also set the start pressure to zero then both pressures 

would be the same and the E30 will not tolerate this and will display a message 

telling you to check your pressure settings.

Mode 1 Stop Pressure

The stop pressure is the pressure at which the E30 will shut down the pump in 

normal operation.  It must be set to some value that is higher than start and trip 

pressures.  The range of adjustment is zero to 2000 kPa or zero to 290 psi in 

increments of 1 kPa or 1 psi.  If you attempt to set the stop pressure to a value 

that is less than the start or trip pressures you will invoke a warning message from 

the E30 to check your pressure settings.

The stop pressure can be set to a minimum of 1 kPa or 1 psi higher than the start 

pressure and the E30 will function.  Normally you would set the difference between 

the starting and stopping pressures to some value that is much greater but for 

some special applications the close operating differential capability of the E30 is 

an invaluable feature and can be used in some circumstances as an alternative 

to the single point snap action pressure switch described in mode 3.

Mode 1 Anti-Cycling

Electric motors are often limited in the number of times they can be safely started 

in an hour.  This is particularly important in the operation of submersible bore 

pumps.  When a motor starts there is an initial inrush of current that produces 

heat in the coils and iron rotor of the motor.  If the frequency of starts is excessive 

the accumulation of heat within the motor can cause severe damage and eventual 

failure of the motor. Submersible bore pump motors are particularly prone to 

damage from excessive cycling (starting and stopping).

Содержание E30

Страница 1: ...KELCO E30 DIGITAL PRESSURE SWITCH PROGRAMMING INSTRUCTIONS KELCO Engineering Pty Ltd Sydney Australia www kelco com au...

Страница 2: ...ng and holding down the P button and pressing the R reset button at the same time Release the reset button while still holding down the P button and then release the P button This process is called pu...

Страница 3: ...ll depend on what level of control is required In order to achieve the best performance from the E30 observe the following basic points 1 Use the least number of functions possible Do not program in f...

Страница 4: ...Anti cycling controls the number of motor starts per hour Y Y Anti cycling sensitivity control to avoid nuisance tripping Y Start the pump at a preset low pressure Y Y Y Stop the pump at a preset hig...

Страница 5: ...ng pressure static or dyamic 1 Bar absolute or 14 7 psi absolute 0 kPa gauge or 0 psi gauge Minimum burst pressure all models 30 Bars 435 psi Trip pressure range Adjustable from 0 to 2000 kPa or 0 to...

Страница 6: ...r extended periods When power resumes the E30 is switched back on and the E30 will automatically boot up and resume running using the settings you recorded in its memory The Three Operating Modes The...

Страница 7: ...e to ignore these pressure fluctuations while still providing loss of pressure protection when a genuine problem occurs If you leave the trip pressure set to zero the E30 reverts to operating like a c...

Страница 8: ...elect to use a remote input switch to trigger the starting and stopping of the pump If you select to use the remote input the E30 will only allow the pump to run while ever the remote switch is closed...

Страница 9: ...run on timer is initially set to 5 seconds by default If you purge the E30 program the run on timer will be reset back to its default 5 seconds Delayed Restart The E30 includes a function called delay...

Страница 10: ...ime or if it successfully starts the pump and subsequently runs dry again the E30 will then go into permanent alarm It will shut the pump down close its relay contacts and display a message on its LCD...

Страница 11: ...ost The batch run in this situation will recommence from the beginning of the set time Mode 1 Trip Pressure The trip pressure can be set to any value from zero to 2000 kPa or from zero to 290 psi depe...

Страница 12: ...he pressure at which the E30 will shut down the pump in normal operation It must be set to some value that is higher than start and trip pressures The range of adjustment is zero to 2000 kPa or zero t...

Страница 13: ...a sensitivity value of 10 and also set to 360 starts per hour one start every 10 seconds maximum If the pump starts 9 times in a row at less than 10 seconds between starts and then does not start aga...

Страница 14: ...function the E30 in pressure guard mode will only operate while the remote input switch is closed The remote switch can be a two position level switch in a remote tank or the contacts of a relay in a...

Страница 15: ...ero to 290 psi depending on the pressure units you have chosen to use The low pressure trip point must be set to some value that is less than the high pressure trip point If you attempt to set the low...

Страница 16: ...tem pressure exceeds this limit for any reason and reaches 2200 kPa or 430 psi the E30 will automatically shut down the system and display a message that its 22 Bar excess pressure limit has been exce...

Страница 17: ...interposing contactor that can be used to switch pump motors of any size Relay 1 has special features built in that allow time for pump motors to wind up and wind down when starting and stopping The...

Страница 18: ...sure This is the differential pressure or difference between the on and off pressure you require The range of adjustment is 7 to 140 kPa or 1 to 20 psi in increments of 7 kPa or 1 psi The higher the v...

Страница 19: ...LCD screen backlight can be switched on manually at any time by pressing and holding down the down arrow button The screen will remain illuminated while ever you are depressing the down button The sc...

Страница 20: ...witch This is because the snap switch mode uses its own unique setting for the alarm relay The seven possible alarm relay configurations are Closed if any Fault Develops In Mode 1 with this option sel...

Страница 21: ...alarm relays contacts will remain open Starts per Hour Setting Exceeded If you intend selecting anti cycling from the main menu then this alarm configuration can provide a set of dedicated contacts t...

Страница 22: ...eering Pty Ltd reserves the right to change the specification of this product without notice Kelco Engineering Pty Ltd accepts no liability for personal injury or economic loss as a consequence of the...

Отзывы: