6.3 Australian Standard Special Instructions
6.3.1 Ground Fault Instructions
The inverter complies with the requirements of IEC 62109-2 article 13.9 on ground fault alarm
monitoring. When the ground fault alarm occurs outside the inverter, the detection circuit inside the
inverter can act in time, and the LED
Alarm
indicator light on, and the fault code "E047" will be
displayed on the inverter screen.
A ground fault affects the security of the inverter. For details, see Table6-1.
6.3.2 PV/QV Mode Setting Instructions
Kehua inverter complies with the AS/NZS 4777.2:2020 standard. The new standard introduced the
volt-watt (PV) and volt-var (QV) response mode to restrict the power output of the inverter in response
to the voltage at its terminals.
Settings for the power quality response modes are shown in Figure6-1.
17/01/01 12:00
Status: STANDBY
Start inverter
Homepage
Main menu
Long press
> Record Query
△
System Set
△
Main menu
Short press
Record Query
△
> System Set
△
Long press
> User
Admin
Long
pre
ss
System set
Password:
0 0 0 0 0 0
0
Password Entry
Password:
0 0 0 1 1 1
1
Password Entry
Short press: reduce number value
Short press: add number value
>Grid Std
Power Calib
△
Long
pre
ss
Engineer Set
QV_Mode
>OFF
ON
QV Mode Set
Long press
QV_Mode
OFF
> ON
QV Mode Set
Short press
ON
OFF
Long press
QV_Mode V1
089.6%
QV Mode Set
Long press: move to next position
Engineer Set
Long
pre
ss
QV_Mode V2
095.3%
QV_Mode V3
103.9%
QV_Mode V4
110.4%
QV_Mode Q1
30%
QV_Mode Q4
-30%
Long press
PV_Mode
OFF > ON
PV Mode Set
ON
QV Mode Set
△
> PV Mode Set
△
Long press
PV_Mode V1
095.3%
PV Mode Set
Long
pre
ss
PV_Mode V2
108.3%
PV_Mode V3
114.7%
PV_Mode P1
100%
PV_Mode P2
100%
PV_Mode P3
020%
> QV Mode Set
△
PV Mode Set
△
> Engineer Set
△
I/O Set
△
> Australia A
Australia B
Australia C
Figure6-1
Settings for the power quality response modes