Table3-1
Wire and terminal specification recommendation value (the power of single power module is
25kVA)
Model
MR3375
MR33125
System max. capacity (kVA)
75
125
A
C
i
nput
AC input current (A)
142
236
Recommended wire diameter (mm
2
)
U/V/W/N
4
×
50
4
×
120
Wire terminal model
DT50
DT120
B
ypas
s i
np
ut
Bypass input current (A)
114
189
Recommended wire diameter (mm
2
)
U/V/W/N
4
×
35
4
×
95
Wire terminal model
DT35
DT95
O
ut
put
Output current (A)
114
189
Recommended wire diameter (mm
2
)
U/V/W/N
(for non-linear load, it needs
to increase the wire diameter
of neutral wire)
4
×
35
4
×
95
Wire terminal model
DT35
DT95
B
at
ter
y i
nput
Nominal discharge current of storage battery (the current of equipped
±
20 pieces of 12V storage battery (480V))(A)
166
277
Max. discharge current of storage battery (the ending discharge
current value <the voltage of each battery is 10.5V> for equipped
±
20 pieces of 12V storage)(A)
190
316
Recommended wire diameter (mm
2
)
+/N/-
3
×
70
2
×
(3
×
70)
Wire terminal model
DT70
DT70
G
roun
di
n
g
w
ir
e
Recommended wire diameter
(mm
2
)
PE
25
50
Wire terminal model
DT25
DT50