KC-P30 x-series
Functions
Configuration manual V4.09
38
© KEBA
Manufacturer
Model
Herholdt
ECSEM113
Janitza
B23 312-10J
Janitza
ECSEM114MID
Siemens
7KT1260
The following meters can be read out directly by the charging station using
Modbus TCP.
Manufacturer
Model
B-control
EM300 LR
B-control
EM300 LRW
Information
Detailed information about the meter installation can be found in the instal-
lation instructions of the meter manufacturer.
5.5.3
Settings
The Modbus TCP feature is disabled by default. If an external meter with a
Modbus TCP network interface has been installed in the system, it must be
configured in the web interface in advance.
Different settings have to be made depending on whether you have a single
charging station or a charging network.
Configuration for a single charging station
The post-meter circuit breaker is designed for a certain amperage. To en-
sure that the charging current can be calculated, the amperage of the post-
meter circuit breaker must be configured by means of the DIP switches in
the charging station connection panel. If the charging station cannot find an
external meter when the Modbus TCP function is enabled, or if the connec-
tion to the external meter is interrupted, the charging current gets reduced to
10 A. This is indicated on the LED bar by orange-colored movement on the
first two segments.
The configuration must be made on DIP switch DSW1. Only one maximum
value, which is less than or equal to the amperage of the post-meter circuit
breaker, can be configured with the following DIP switches:
DSW1.4 to DSW1.5
Amperage
Illustration
25 A