5
3.
Screw-in Version
The screw-in variant consists of the HSP5/485 operator 00.F5.060-9001 and a cable
00.F5.0C0-3xxx.
HSP5 interface
of the operator
Special cable
with
converter in the
plug connector!
HSP5 operator
00.F5.060-9001
Cable: 00.F5.0C0-3xxx
The part No.determines the cable length
X6A
Cable color Terminal
white
1
brown
2
green
3
yellow
4
grey
5
pink
6
blue
7
red
8
black
9
purple
10
• Disconnect inverter/servo from power.
• Remove standard/field bus operator from the inverter/servo, install it at required
place and lay the cable from here to the inverter/servo. Keep distance from motor/
supply cable.
• Screw off the HSP5/485 operator (4 screws from the bottom).
• Reduce one side of the cable to required length, strip 2 cm and turn down backwards
the cable shield.
• Strip the individual cores 5mm and connect it in accordance with table to terminal
X6E of the HSP5/485 operator.
ATTENTION: Exchanging the cores, especially for terminal 10, can lead to
the damage of the converter electronics!
• Attach the cable with the enclosed cable tie in front of the terminal. Pay attention
that the fold back cable shield only has contact to the metallized surface and not to
the terminal or the solder pads at the bottom edge. Close the operator.
• Screw enclosed bolts and washers in the back of socket X6A of the standard/field
bus operator. Plug-in and tighten side 2 of the cable into this socket.
• Put on HSP5/485 operator onto inverter/servo.
• Supply voltage for inverter/servo.
Installation
HSP5/485 Operator
Standard or
fieldbus operator
X6E