3.2.1 Technical data of the charging units H6
Device size
00
Version 1
00
Version 2
Housing
b / P
b / P
Input data
Rated input voltage
U
N
/ V
400 (UL: 480)
Input voltage range
U
in
/ V
320…480
Mains frequency
f
N
/ Hz
50/60 ±2
Mains phases
3
Approved mains forms
TN
Max. permissible mains fuse
I
_max
/ A
10
Supply cable section
Ø / mm²
1.5
DC output data
Output voltage range
U
_dc
/ V
452…840
Rated output current
I
outN_dc
/ A
20
Output data precharging
Rated output voltage
U
outN_dc
/ V
565
Output voltage range
U
_dc
/ V
452…680
Overvoltage switch-off
U
OP_dc
/ V
840
Max. precharging current
I
O_dc
/ A
5
braking transistor (GTR7)
Max. brake power (switching cycle=40%)
P
_max
/ kW
46.2
Max. braking current
IB
_max_dc
/ A
146
176
Min. braking resistor
RB
_min
/ Ω
6 (-10 %)
5 (-10 %)
Connection cross section
mm²
16
Response voltage
U
_dc
/ V
780
Switching frequency
f
SN
/ kHz
4
Switching cycle based on 120s cycle time
ED
/ %
40
30
Other data
Power dissipation interior
P
Dint
/ W
5
Max. heat sink temperature
THS
/ °C
80
60
Insulation resistance @
U
dc
= 500 V
R
sio
/ MΩ
> 5
Supply control unit
Input voltage
U
CU_dc
/ V
24 (±10 %)
Input current
1)
I
CU_dc
/ A
0.2
Table 8:
Technical data of the charging modules H6
1)
Input current, if no digital input is set. At max. load at the digital outputs the input current can be increased
up to max. 1 A.
29