GB - 8
General
1.7
Transport instructions
Transport of heat sinks with an edge length of ≥ 75 cm:
Transport by fork-lift truck can lead to a deflection of the heat sink.This can have the aging or
destruction of internal components as a result.
Attention
Transport instructions must be observed.
To avoid damage, the inverter may only be transported on suitable pallets.
1.8
Installation instructions
1.8.1 Cooling systems
The KEB COMBIVERT F5/F6 is available for different cooling systems:
Heat sink with cooling fan (mounted version)
The standard version is delivered with heat sink and cooling fan.
Special versions
The dissipation of power loss must be guaranteed by the machine builder.
Flat rear
There is no heat sink at this version. The unit must be mounted on an appropriate ground for
heat dissipation.
Water cooling
This version is dimensioned for the connection to an available cooling system. The dissipa-
tion of the power loss must be ensured by the machine builder. In order to avoid moisture
condensation, the minimum inlet temperature may not decrease the ambient temperature.
The max. inlet temperature may not exceed 40°C. No aggressive coolant shall be used.
Measures against contamination and calcination must be done externally. We recommend a
pressure of 4 bar on the cooling system.
Convection (trough-mount version)
In this version the heat sink is placed externally with a cutout in the control cabinet.
CAUTION
!
DO NOT TOUCH!
Hot Surfaces
© 2005 KEB
In case of burn, cool inflicted area
immediately and seek medical attention.
Heat sinks can reach temperatures, which can cause burns when
touching. If in case of structural measures a direct contact cannot
be avoided, a warning notice "hot surface" must be mounted at the
machine.