33
Site altitude max. 2000m. With site altitudes over 1000m a power reduction of 1% per
100m must be taken into consideration.
2.3.2 400 V-class
Product Description
12
13
14
15
16
E
E
E
E
E
3
3
3
3
3
[kVA] 6,6 8,3
11
17
23
[kW]
4
5,5
7,5
11
15
[A] 9,5
12
16,5
24
33
[A] 17 21,6 29,7
36 49,5
[A] 21 25,9 35,6
43
59
[A] 13
17
23
31
43
[A] 20
25
25
35
50
[kHz] 16
16
8
4
2
[kHz] 16
16
16
16
4
[W] 300 250
320 350 330
[Ohm] 82
39
39
39
25
[Ohm] 150 110
85
56
42
[A] 10
21
21
21
32
[V]
305...500 ±0
[Hz]
50 / 60 ±2
[V]
400
1)
[V]
3 x 0...U
N
[Hz]
0...400
[mm²] 2,5
4
4
6
10
[m]
100
Inverter Size
Housing size
Phases
Output rated power
Max. rated motor power
Output rated current
Max. short time current
OC-tripping current
Input rated current
Max. permissible mains fuse (inert)
Rated switching frequency
Max. switching frequency
Power loss at rated operation
Min. braking resistor
Typ. braking resistor
Max. braking current
Mains voltage U
N
Mains frequency
Input rated voltage
Output voltage
Output frequency
Min. motor line cross section
Max. motor line length (shielded)
1)
at mains voltage > 460 V multiply the nominal current with factor 0.86
Содержание COMBIVERT F5 Series