4 Unit Data
Information on the dimensioning =>
.
Device size
14
16
18
20
22
Housing size
E
G
H
R
R
Cooling mode (L=air; W=water)
L
L
L
L
L
W
Input data
Mains phases
3
Permitted mains forms
1)
TN system
Rated input voltage
U
N
/ V
400
Input voltage range
U
in
/ V
340…480 ± 0%
Mains frequency
f
N
/ Hz
50 / 60 ± 2
Rated input power
S
N
/ kVA
11
23
35
52
80
Rated input current
I
N
/ A
16.5
33
50
75
2)
115
2)
Max. permissible mains fuse type gR / aR
25
50
80
100
160
Output data
Rated output voltage
U
outN_dc
/ V
680
Output voltage range
3)
U
_dc
/ V
530…840
Overvoltage switch-off (E.OP)
U
OP_dc
/ V
840
Power supply/regenerative rated current
4)
I
outN_dc
/ A
16.5
33
50
75
115
Max. regenerative DC current 30 s
I
out_max_dc
/ A 29.7
49.5
75
112
172
207
Rated switching frequency
5)
f
SN
/ kHz
8
Max. switching frequency
f
S_max
/ kHz
16
Other data (referring to the rated data)
Overcurrent cut-off (E.OC)
I
OC
/ %
216
180
180
180
180
216
Overload current (E.OL) 30 s
I
OL
/ %
180
150
150
150
150
180
Max. permissible DC link capacity
C
ext
/ mF
–
–
–
50
50
I
AIC
/ A
29
6)
57
29
226
226
Max. external charging current (=>
I
ext
/ A
75
6)
135
322
–
–
Max. permissible total charging current (=>
)
I
pre
/ A
104
6)
192
351
226
226
)
Type
A1
A2
A1
D1
Permissible DC fuses
Short-circuit factor at the connection point (
S
kn
/
S
N
)
15 <
S
kn
“ < 350
Power dissipation at rated operation
P
BR
/ W
295
449
525
830
1400
Max. heat sink temperature
t
_max
/ °C
90
90
90
90
90
60
Table 7:
Device data
1)
Operation on a local limited IT system with sine-wave EMC filter is possible.
2)
The input current of the drive converter is limited, if necessary to the rated current of the AIC / LCL
filter.
3)
The operation is dependent on the voltage setpoint and the U
OP
).
4)
Measured at a reference voltage of 680 V DC.
5)
Must be set to 8 kHz for AIC operation (factory setting 4 kHz) !
6)
At ambient temperature T
a
of 45°C.
27
UNIT DATA