3 Technical Data
3.1 Operating conditions
3.1.1 IP protection classes
Filter type
0D
0H
0L
0P
0S
0X
0y
Protection classes
IP 00
IP 20
IP 20
IP 20
IP 20
IP 20
IP 20
Table 1:
IP protection classes
3.1.2 Climatic conditions
Storage
Standard
Class
Notes
Surrounding temperature
1K4
-25…55 °C
Relative humidity
1K3
5…95 % (without condensation)
Storage height
–
–
Max. 3000 m above sea level
Transport
Standard
Class
Notes
Surrounding temperature
2K3
-25…70 °C
Relative humidity
2K3
95 % at 40 °C (without condensation)
Operation
Standard
Class
Notes
Surrounding temperature
3K3
5…40 °C (extended to -10…45 °C)
Coolant inlet
temperature
Air
–
–
5…40 °C (-10…45 °C)
Relative humidity
3K3
5…85 % (without condensation)
Version and degree of
protection
=>
Protection against foreign material > ø12.5 mm
No protection against water
Non-conductive pollution, occasional conden-
sation when PDS is out of service.
Site altitude
–
–
Max. 2000 m above sea level
• With site altitudes over 1000 m a derating
of 1 % per 100 m must be taken into con-
sideration.
Table 2:
Climatic conditions
15
OPERATING CONDITIONS
Содержание COMBILINE Z1I05-1001 Series
Страница 2: ......