KE2 Temp + Defrost Скачать руководство пользователя страница 5

Q.1.20 February 2016

Page 5

KE2 Temp 

+ Defrost 

(pn 20611)

For 

Medium Temperature

 Applications with 

Air Defrost

Installation Manual

© Copyright 2016 KE2 Therm Solutions, Inc., Washington, Missouri 63090

Access Setpoint mode by pressing and holding the             button until 

tS (temperature setpoint) displays on the screen   

ENTER

Use the        up and      down arrows to scroll through the available setpoints.   

ENTER

Press              to view the current setting.

Indicator lights

Red  light - Not used
Yellow light - non-critical alarm (system running)
Green light - compressor on
Green flashing - compressor waiting on timer to start/stop

tS   =   Temperature Setpoint
diF   =   Differential
CSH   =   Maximum Compressor Starts/Hour
dPd   =   Defrost Per Day

 tOd

 d1

 d2

 d3

 d4

 d5

 d6

 d7

 d8

 d9

 d10

 d11

 d12

dFt   =   Defrost Time
HAO  =   High Alarm Offset
LAO  =   Low Alarm Offset
tAd   =   Temp Alarm Delay
Adr   =   Mod Bus Address
Unt   =   Units for temp display (FAH or CEL)

Setpoints

Hold for manual defrost

therm

solutions

.

KE2 

Temp

Use the        up and      to change the setpoint

ENTER

Press              to move between the digits to accelerate the changes.

ENTER

Press              and hold to confirm each setpoint change

BACK

Press              to escape.

 Only visible if CUS (custom) is 

selected for dPd (Defrost per day) 

See page 7 for detailed setup 

instructions.

Alarms 

When amber LED is lit:
SSA
   =  Shorted Sensor Alarm
OSA  =   Open Sensor Alarm
HtA  =   High Temp Alarm
LtA   =   Low Temp Alarm

Programming the Controller

Many applications of the KE2 Temp + Air Defrost can use the 

controller’s preset defrosts per day. This automatically spaces 

the defrosts throughout the day, based on the number of de-

frost cycles selected. The user has the ability to change the 

number of defrost cycles performed by changing the Defrost 

per Day setpoint from 0 to 12.

 

For more specific applications, the KE2 Temp has the option to 

schedule each individual defrost at a specific time of day.

 

KE2 Temp + Air Defrost Basic Navigation

Understanding the KE2 Temp + Air Defrost’s menu structure 

will simplify configuration.

In Figure 1 shows the basic button functions, as well as a list 

of basic setpoints.

Figure 1

Содержание Temp + Defrost

Страница 1: ...ltage wires matched to the load of the liquid line solenoid compressor and the controller wire labeling numbers colors etc additional wire ties 18 gauge twisted shielded pair if extending sensor wires...

Страница 2: ...plicity in mind The controller accepts 120V 208 240V to power the controller and 12V 240V solenoid voltage via the liquid line solenoid relay through the lower conduit connection The temperature senso...

Страница 3: ...the controller will be breaking one leg of the power One leg of incoming power L1 supply for the liquid line solenoid should be connected to the common terminal of the liquid line solenoid relay the...

Страница 4: ...e temperature sensor terminal is located on the cover s circuit board and is permanently attached The temperature sensor input consists of the right two terminals Although the terminals are labeled an...

Страница 5: ...tions KE2 Temp Use the up and to change the setpoint ENTER Press to move between the digits to accelerate the changes ENTER Press and hold to confirm each setpoint change BACK Press to escape Only vis...

Страница 6: ...mum Default Maximum tS Temperature Setpoint 50 F 45 C 35 F 100 F 38 C diF Differential 1 F 1K 2 F 30 F 17K CSH Maximum Compressor Starts Hour 5 Off 6 10 dPd Defrost Per Day 0 6 12 CUS d12 Start time o...

Страница 7: ...the nearest 10 minutes See exam ples below Examples then press Use the up arrow and down arrow to set the time STEP 7 Press the button to save set tings and return to the main screen room temp will b...

Страница 8: ...rm Solutions 12 Chamber Drive Washington MO 63090 1 888 337 3358 www ke2therm com Q 1 20 February 2016 Page 8 KE2 Temp Defrost pn 20611 For Medium Temperature Applications with Air Defrost Installatio...

Отзывы: