background image

9

Start to perform attachment construction after checking the power supply of product. 
Use hanging bolts and foundation bolts that have sufficient intensity.
Recommending installing a filter so that dust etc. may not be inhaled to a suction side. 
(Be careful of the air volume down by the filter pressure loss.)
When the combustion appliance is being used in the room, please prepare a big suction mouth independently.
When the duct is connected to the outdoors, a pipe hood should be installed at the outdoors end, and the duct should be 
installed 1/100 or more downward pitches. 
(Prevent rain water not to come to fan side.)
When installing  ducts, hang the ducts from ceiling so that the duct weight is not applied to fan. 
Please don't carry out the following ductworks. 

Roll an aluminium tape to connecting part not to carry out an air leak after installing and fixing fan and ducts.
When fan operating is stopped, keep the duct inside wind flow down even if there are outside flowing pressure, so as to keep 
the wheel not to rotate. Please attach an electric damper, the backflow  prevent damper, etc. 
Please do not use or set this fan at the place as follows, outdoor, the place which requires water, the place where steam 
generates,  the place where corrosive gas may generate, and the place where chemicals are used. 
Don't make a hole to the fan casing. In the casing  there are electric parts inside. If a hole is made to the fan casing it may be 
damaged.
This fan is not used like the place as follows. The place where heat, oil mist, steam or humidity gas 
generate or exhaust gas from pool or spring ingredient.
(Environmental conditions (ambient and air conditions): -10 to +40 deg C, relative humidity 85% or less)
When you supply cold air into the room in the winter, if there is any possibility that condensation may form on the connection 
part of the duct or the surface of the product, be sure to always carry out thermal insulation treatment on them.
Carefully install the air supply fan and exhaust fan to prevent short circuiting.
Install the fans horizontally. You cannot install them upside down or in a vertical orientation.

1.Before installation

Check the following.

Confirmations

Is there any breakage or deformation?
Is there product as per your order?

Installation Instructions

Wear protectors as gloves and helmets during installation and maintenance.
May cause injury or burn.

CAUTION

1 Bending 

extremely

2 Bending 

repeatedly

3  Making duct 

diameter too small

4  Bending very near 

to the fan mouth 

Separate 1m or more 
from the fan mouth. 

Bellows

Содержание K25DSF2NET

Страница 1: ...Safety Precautions on page 2 4 prior to use K35DSM2NET K40DTL2BET Table of Contents Safety Precautions 2 4 Names and Dimensions of Component 5 Maintenance and Inspection 6 Periodic Check and Maintenance 7 Specifications 8 Installation Instructions 9 Rear cover page 1 Before installation 9 2 Installation 10 3 Power cord connection 11 Rear cover page Compact Axial Flow Fan Operating Instructions Inc...

Страница 2: ...t all components and parts If they fall it may cause an injury When combustible gas leakage occurs open the windows to make air circulate When you start the fan a spark of the electrical contacts may cause an explosion or fire This fan should be installed so that the metal parts of the product and mounting screw do not contact any metallic members in the wall such as metal laths wire laths and met...

Страница 3: ...ils or if an electricity leakage occurs in it it may cause an electric shock Stop immediately the operation in case of any abnormality noise vibration smell and request for repair May cause unexpected accidents Wear protectors such as gloves and helmets during installation and maintenance May cause injury or burn Electrical wiring ducting and installation should be done by specialist Insufficient ...

Страница 4: ... or sucking the obstacle Don t operate with the wheel to which much dust has been adhered May cause wheel breakage or motor burnout Do not install the main body and indoor air supply entrance at the place with harmful gas of Acid Alkali organic solvent paint etc gas including corrosive substance chemical factory facility for research etc The poison erosion on internal main body quality drop from g...

Страница 5: ... A 350 410 480 540 B 197 206 206 218 C 22 21 5 26 25 5 D 248 298 347 395 E 400 460 525 588 F 366 426 491 554 G 350 415 480 546 H M8 M8 M8 M10 I 32 32 32 34 J 9 9 9 11 Parts name Casing A Casing B Motor Wheel Guide vanes Hanger fittings Drain gum Q ty 1 1 1 1 4 2 1 Material Steel Steel Alminum Steel Steel Gum No 1 2 3 4 5 6 7 8 Parts name Casing A Casing B Motor Wheel Guide vanes Hanger fittings Te...

Страница 6: ... years Inspection Criteria Indication Maintenance Remarks 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 1 Entire fan Update equipment 2 Casing Guide vanes 3 Wheel 5 Terminal Check noise and vibration by hearing and touching Check attaching screws for looseness with tool Check the appearance visually Check noise and vibration by hearing and touching Check the appearance visually Check rotation visually with ...

Страница 7: ...of use operation time per day etc 5 Abnormal conditions from when and how it occurs 6 Handling air for general ventilation or for clean air and intended use symptom Insufficient air flow Excessive vibration Overheated motor Run abnormally Action Excessive noise Poor foundation Faulty installation Outside range of rated voltage Contact between rotary and stationary parts Sucked in objects Adhered d...

Страница 8: ...K25DSF2NET Single phase 220 240V 4 25 Hi 600 720 0 19 0 17 0 24 0 22 34 38 41 0 42 0 51 0 54 0 50 5 53 5 4 7 Lo 550 650 0 14 0 12 0 17 0 18 27 29 39 5 41 5 49 0 52 0 48 5 51 5 K28DSM2NET Single phase 220 240V 4 20 Hi 1194 1224 0 25 0 28 0 32 0 35 51 62 44 5 45 5 54 5 55 5 54 0 55 0 8 5 Lo 1050 1062 0 24 0 26 0 30 0 32 55 61 42 0 43 0 52 0 53 0 51 5 52 5 K35DSM2NET Single phase 220 240V 4 60 Hi 201...

Страница 9: ...e which requires water the place where steam generates the place where corrosive gas may generate and the place where chemicals are used Don t make a hole to the fan casing In the casing there are electric parts inside If a hole is made to the fan casing it may be damaged This fan is not used like the place as follows The place where heat oil mist steam or humidity gas generate or exhaust gas from...

Страница 10: ...g For power connecting removing or setting the terminal cover Install the exterior duct in over 1 100 declining slope toward outer side Make the access door opening to the side of power cord or terminal cover 450mm or more Check the air direction referencing the name plate Carry out heat insulation processing to fan or ducts when dew condensation may take place Connect the circular duct to the ada...

Страница 11: ...will stop Once the fuse blows the motor cannot restart itself that is it cannot rotate Locate and remove the cause of the error and replace the motor Note that an unstable or temporarily installed power supply may cause the thermal fuse to blow and the motor may stop during a trial run After wiring check the rotation direction in case of three phase motors Electric wiring cautions Installation Ins...

Страница 12: ...against the terminal cover biting power cord Power supply Fan body The tip of the power cord which is not used must be insulated Protection tapes or covers for insulation Terminal For reference only Sold at parts stores K40DTL2BET K40DTH2BET K45DTT2BET K45DTH2BET The illustration shows an example of connecting for high power operation For low power operation connect cords according to the Wiring D...

Отзывы: