KBR multicomp F144-NC-1V1C6DO6RO-2
Control and display panel
Extras menu
THD limit:
8 %
Harmonics monitoring:
Activated by set limit
Contactor stage operating cycle limit:
80000
Operating cycle count:
Activated by set limit
Scanning frequency:
Automatic
Stage power monitoring:
Deactivated
Contrast setting: 4
Low-load limit: 15 mA
Low-load delay: 60 minutes
Other
Recovery target CosPhi:
1.00, cannot be changed
Stage switching mode:
Automatic
The controls in the compensation systems are preset.
The following need to be checked or set:
target CosPhi in accordance with the energy supplier regulations
(for kVA tariff CosPhi = 1)
Primary current and secondary current in accordance with input current transformer.
If required, voltage transformer ratio