V7.00
24449_EDEK
ZA0031-2619-1_DE-EN
9
Terminal:
41 (K1) to 45 (K5):
Non-floating relay contacts
These contacts are used as control outputs for the capacitor
switching contactors. As long as the device is dead and for
stages that are not hooked up, the contacts are open. Maximum
switching capacity 2A at 250V AC.
51 (-) and 52 (+):
Temperature sensor input
A temperature sensor, e.g. PT1000, can be connected to this
input to measure the switchgear cabinet temperature.
Temperature measuring range of – 20°C to 100°C +/- 2°C.
90 (earth):
91 (A)
92 (B)
Interface connection
For communication on the eBus or Modbus
3
Start-up guidelines for the multicomp D6-xxx-7
This guideline helps you to correctly start up the compensation controller multicomp
D6-xxx-7. It provides you with step-by-step instructions to help you find the options
relevant for you in the operating instructions.
To begin with, there are two cases in which the start-up procedure for the
multicomp D6-xxx-7 differs.
Case 1:
You have bought a complete compensation system from KBR, and the controller
is already installed. If this is the case, certain settings are already preconfigured in the
controller.
Case 2:
You only bought the controller, or the controller with additional modules
(multisio D2-1T2RO, multisio D2-4RO, multisio D2-4CI and multimess D4) and individual
capacitor stages, but the system is not assembled. In this case, the controller is delivered
with the default settings (refer to chapter Default settings) and has thus not been precon-
figured.