KBR multicomp F144-3 6DO/12DO
Error message dialog:
Missing measuring voltage
The setting Message or
Missing stage power
Alarm relay or Message and
PFC too small
Alarm relay or Off
THD too high
is identical for all errors!
No measuring current
Light load
Temperature switch-off
Extras:
Display language
German, English, French, Spanish
Limit THD
0 to 10%, harmonics monitoring can be dis-
abled (0%)
Scanning frequency
Automatic, fixed 50 Hz, fixed 60 Hz
Stage power monitored
Yes, No
Reset Run
Contrast setting
0 to 10
Brightness setting
0 to 9
Dimmer brightness
0 to 9
Light load limit
15 mA, 50 mA
Light load delay
1 minute to 60 minutes
Temperature measurement
On / Off
Output 6 or 12
(depending on the
controller version)
Compensation stage, fan output
Switching threshold fan on
> 0 °C to 60 °C
Switching threshold fan off
0 °C to 60 °C
Switching threshold system off > 0 °C to 60 °C
Switching threshold system on 0 °C to 60 °C
Bus mode
Modbus (eBus for production)
Learning mode menu display On / Off
Touch tones
On / Off
Control and display panel