KBR D2-1DI2DO-1 Скачать руководство пользователя страница 7

V1.00

7

26415_EDEBD

A0305-2321-1_EN

Introduction

Technical data

Input data:

Input voltage

power supply

100 – 240 V +/- 10% ,DC/50/60 Hz, max. 
3,5 VA

Power optocoupler

Switching level  
1-Signal („H“) >10mA to <27mA
Switching level 0-Signal („L“) < 2mA

Transmission frequency f

grenz

 (ohmic load)

10 Hz

Input circuit

Overvoltage protection, Reverse polarity protection, RC element,  
Operating display (LED yellow), Voltage indicator(green)

Output data:

Operating voltage range

15 to 120 VDC

Continuous load current

2x 0,75 A

Voltage drop at max. load current

1,4 V DC

Output circuit

Reverse polarity protection, overvoltage 
protection floating, 2-wire connection

Standards and miscellaneous

Ambient 
conditions

Standards

DIN EN 60721-3-3:1995-09 + DIN EN721-
3-3/A2:1997-07; 3K5 +3Z11; (IEC721-3-
3;3K5 + 3Z11)

Operating temperature

K55 (-5°C ...+55°C)

Air humidity

5%...95% non-condensing

Storage temperature

K55(-25°C...+70°C)

Operating height

0…2,000 m above sea level

Electrical 
safety

Standards

DIN EN 61010-1:2011-07

Protection class

II

Overvoltage category

Power supply

CAT III: 300V

Isolation voltage

Input/ Output

4 kV

Output / Output

2,5 kV

Rated surge  
voltage

4 kV

Protection type

Standards

IP 20 according to  
DIN EN 60529:2014-09

Содержание D2-1DI2DO-1

Страница 1: ...321 1_EN System I English You can find the instructions for your KBR device at our download center https www kbr de de dienstleistungen download center Quick guide Technical parameters D2 1DI2DO 1 Pulse doubler multisys ...

Страница 2: ...bau GmbH does not accept any liability for any loss or damage resulting from printing errors in or changes to this manual In addition KBR Kompensationsanlagenbau GmbH does not accept any liability for any loss or damage caused by defective devices or devices manipulated by the user Copyright 2021 by KBR Kompensationsanlagenbau GmbH Subject to change Table of Contents ...

Страница 3: ...rs explain the technical details of the device and show how damage can be avoided through proper installation and commissioning 1 1 User Manual This user manual must be accessible to the user at all times e g in the switchgear cabi net Even if the device is resold to third parties the manual remains an inherent part of the device Although the utmost care has been taken in writing this user manual ...

Страница 4: ...age may occur if the appropriate safety pre cautions are not taken NOTE Note is an important piece of information on the product its operation or the respective part of the user manual to which special reference is being made Disclaimer The contents of these user manual have been carefully reviewed in terms of the hardware and software described However deviations cannot be excluded and therefore ...

Страница 5: ...ormation given in the connection diagram see Connection diagram and that the connecting cables are not live When wiring always ensure that all cables used are neither damaged nor faulty and observe correct polarity Proper and safe operation of the product requires correct transport storage installation and assembly as well as careful operation and maintenance If the device has any visible damage i...

Страница 6: ...Integrated power supply One input Two outputs Top hat rail housing 2 Wiring diagram 2 1 83 82 81 80 Pulse generator EVU meter or KBR multimess D6 xxx 5 etc Pulse input Pulse output 2 Pulse output 1 51 50 Supply voltage 100 240V AC DC 10 LED Pulse LED Power 1K Side view from right Top view ...

Страница 7: ...5 A Voltage drop at max load current 1 4 V DC Output circuit Reverse polarity protection overvoltage protection floating 2 wire connection Standards and miscellaneous Ambient conditions Standards DIN EN 60721 3 3 1995 09 DIN EN721 3 3 A2 1997 07 3K5 3Z11 IEC721 3 3 3K5 3Z11 Operating temperature K55 5 C 55 C Air humidity 5 95 non condensing Storage temperature K55 25 C 70 C Operating height 0 2 00...

Страница 8: ...Am Kiefernschlag 7 D 91126 Schwabach Germany T 49 0 9122 6373 0 F 49 0 9122 6373 83 E info kbr de www kbr de KBR Kompensationsanlagenbau GmbH 26415_EDEBDA0305 2321 1_EN ...

Отзывы: