6
See Figure 1 on page 5. Also see Section 4 – Important Application Information, on page 20.
WARnInG! Disconnect main power before making connections to the drive.
1.1
AC Line Connection –
Wire the AC line input as described below and as shown in Figure 16
on page 31. See Section 9.1, on page 30.
Application Note: Do not wire this drive to a GFCI. If operation with a GFCI is required,
contact our Sales Department.
Models KbVf-13, 14 –
Rated for 115 Volt AC line input only. Wire the single-phase AC line
input to Terminals “L1” and “L2”.
Models KbVf-23, 24 –
Rated for 208/230 Volt AC line input only. Wire the single-phase AC
line input to Terminals “L1” and “L2”
Models KbVf-21D, 22D, 23D, 24D, 26D* –
Rated for 208/230 Volt AC line input with
Jumper J1 (on upper PC board) set to the “230V” position (factory setting). Rated for 115 Volt
AC line input with Jumper J1 (on upper PC board) set to the “115V” position. Wire the single-
phase AC line input to Terminals “L1” and “L2”
*On Model KBVF-26D, Jumper J1 is labeled “115VAC” and “230VAC”.
Models KbVf-23P, 24P –
Rated for 208/230 Volt AC line input. Wire the 3-Phase AC line
input to Terminals “L1”, “L2”, and “L3”.
1
QUICK-START InSTRUCTIOnS
Important – You must read these simplified instructions before proceeding. These instruc-
tions are to be used as a reference only and are not intended to replace the details pro-
vided herein. You must read the Safety Warning on, pages 8 and 9, before proceeding.