16
F. Control Mode Selection (J6) –
Jumper J6
is factory set to the “SPD” position for
Speed Control Mode . For Torque Control
Mode, set Jumper J6 to the “TRQ” posi-
tion. See Figure 22.
G. Torque Control Mode Selection (J7) –
Jumper J7 is factory set to the “S/L” posi-
tion for Speed Mode and Linear Torque
Mode. For Non-Linear Torque Mode, set
Jumper J7 to the “NL” position. See Figure
23. (See Section VI, on page 18.)
H. Current Limit Mode Selection (J8) –
Jumper J8 is factory set to the “TCL” posi-
tion for Timed Current Limit operation. For
Non-Timed Current Limit operation, set
Jumper J8 to the “NTCL” position. See
Figure 24.
TCL (Timed Current Limit) –
When
Jumper J8 is set to the “TCL” position, the
control will go into Stop Mode after it is in
overload for a predetermined amount of
time (set by the TCL trimpot).
Resetting the Control after TCL –
To
reset the control after it has gone into TCL,
set the Start/Stop Switch to the “STOP”
position and then momentarily to the
“START” position or disconnect and recon-
nect the AC line. If the Start/Stop Switch is
jumpered (START and RET terminals con-
nected), the control must be restarted by
disconnecting and reconnecting the AC
line. If the Power On/Off Switch is
installed, set it to the “OFF” position and
then back to the “ON” position.
Warning!
When the control
shuts down in TCL, the AC line
voltage is still present in the control.
NTCL (Non-Timed Current Limit) –
When Jumper J8 is set to the “NTCL” posi-
tion, the control will not go into Stop Mode
after it is in overload.
Note:
The TCL trimpot will have no affect
when Jumper J8 is in the “NTCL” position.
I.
Stop Mode Selection (J9) –
Jumper J9 is
factory set to the “RTS” position, for
Regenerate-to-Stop Mode. For Coast-to-
Stop Mode, set Jumper J9 to the “CTS”
position. See Figure 25.
J. Run Relay Output Mode Selection
(J10) –
Jumper J10 is factory set to the
“NO” position for normally open relay output contacts at Terminal Block TB3. For normally
closed relay output contacts, set Jumper J10 to the “NC” position. See Figure 26.
J10 Set for
Normally closed Run
Relay Output Contacts
J10 Set for
Normally Open Run
Relay Output Contacts
(Factory Setting)
J9 Set for
Coast-to-Stop Mode
J9 Set for
Regenerate-to-Stop Mode
(Factory Setting)
FIGURE 25 – STOP MODE
SELECTION
J8 Set for
Non-Timed Current Limit
J8 Set for
Timed Current Limit
(Factory Setting)
J6 Set for
Torque Control Mode
J6 Set for
Speed Control Mode
(Factory Setting)
J6
SPD
TRQ
J6
SPD
TRQ
FIGURE 22 – CONTROL MODE
SELECTION
J7 Set for
Speed Mode and
Linear Torque Mode
(Factory Setting)
J7 Set for
Non-Linear Torque Mode
J7
S/L
NL
J7
S/L
NL
FIGURE 23 – TORQUE MODE
SELECTION
J8
TCL
NTCL
J8
TCL
NTCL
FIGURE 24 – CURRENT LIMIT MODE
SELECTION
J9
CTS
RTS
J9
CTS
RTS
!
J10
NO
NC
J10
NO
NC
FIGURE 26 – RUN RELAY OUTPUT
MODE SELECTION