KBBC SERIES OPERATING INSTRUCTIONS

 

 
 

(A40140) – Rev. A00 – 6/10/2014 

Page 2 of 4 

TABLE 1 

ADJUSTABLE TRIMPOTS 

Trimpot Range 

Description 

T-BRK

1

0.2

2.5

 

Timed Brake Delay (T-BRK): 

Allows adjustment of the delay time before the brake engages after the control is put into the stop or brake mode. 
Stop or brake is initiated by opening the Enable Switch or Key Switch or by closing inhibit terminals. 

Adjustment Range: 

0.2 – 2.5 Seconds; 

Factory Setting: 

1 Second 

CL

150

0

200

 

Current Limit (CL): 

Allows adjustment of current limit setpoint. Typically set to 1.5 times the full load current rating of the motor. When 
the control is in Current Limit, the STATUS LED will illuminate red. 

Adjustment Range: 

0 – 200% of Jumper JB Setting; 

Factory Setting:

 150% 

0

IR

4

25

 

IR Compensation (IR): 

Allows adjustment of load compensation for different motors. Smaller motors require more compensation to 
overcome losses in armature winding. Typically set by checking No Load to Full Load speed changes. 

Adjustment Range: 

0 – 25 Volts DC;

 Factory Setting: 

4 Volts DC 

2

DECEL

0.1

15

 

Deceleration (DECEL): 

Allows for controlled deceleration from full speed to zero speed. Decel works with all stop modes except inhibit. 
When inhibit is used, the DECEL Trimpot has no effect, output will go to zero in 0.1 seconds. 

Adjustment Range: 

0.1 – 15 Seconds;

 Factory Setting: 

2 Seconds 

2

ACCEL

0.1

15

 

Acceleration (ACCEL): 

Allows for controlled acceleration from zero to full speed. Acceleration is active in any turn-on condition, including 
Enable, Key Switch, or release of inhibit. 

Adjustment Range: 

0.1 – 15 Seconds;

 Factory Setting: 

2 Seconds 

MIN

0

30

 

Minimum Speed (MIN): 

Sets the minimum speed the motor will run. 

Adjustment Range: 

0 – 30% Base Speed;

 Factory Setting: 

0% 

 

RMAX

50

100

 

Reverse Maximum Speed (RMAX): 

Limits the maximum allowable speed in the reverse direction. 

Adjustment Range: 

50 – 100% Base Speed;

 Factory Setting: 

100% 

FMAX

60

100

 

Forward Maximum Speed (FMAX): 

Limits the maximum allowable speed in the forward direction. 

Adjustment Range: 

60 – 100% Base Speed;

 Factory Setting: 

100% 

 
 

TABLE 2 

RUN RELAY OPERATION 

Connector P5 

Description 

 

Run Relay Output Contacts Selection (P5):

 Provides Normally Open or Normally Closed relay output contacts 

(use Jumper J8 to select N.O. or N.C. contacts). The Run Relay is engaged when the control is in the Run Mode. 
The Run Relay is disengaged when the control is in the Stop Mode or for any fault condition (Main Speed 
Potentiometer Fault (open lead), Over Temperature Fault, Overvoltage Fault, Undervoltage Fault, Motor Brake 
Fault, Internal Fault (micro failure), and Timed Current Limit. 

 
 

TABLE 3 

DIAGNOSTIC LED INDICATORS 

LED Description 

 

Power On:

 This green LED is illuminated when the Key Switch is engaged. 

 

Status:

 Both green and red LEDs are used to indicate control status. See Table 4 on page 3. 

 

 

Содержание KBBC Series

Страница 1: ... a connection must be made between the red wire of Connector P1 Terminal 3 and quick connect Terminal B for the control to operate 2 To reset the control in wig wag mode return the Main Speed Potentiometer to the center position 3 Run Forward and Run Reverse Switches are not used in wig wag operation 4 If wiring a fuse or circuit breaker it must be wired in the location shown immediately after the...

Страница 2: ...ed the DECEL Trimpot has no effect output will go to zero in 0 1 seconds Adjustment Range 0 1 15 Seconds Factory Setting 2 Seconds 2 ACCEL 0 1 15 Acceleration ACCEL Allows for controlled acceleration from zero to full speed Acceleration is active in any turn on condition including Enable Key Switch or release of inhibit Adjustment Range 0 1 15 Seconds Factory Setting 2 Seconds MIN 0 30 Minimum Spe...

Страница 3: ...Limit J3 Non Timed Current Limit Timed Current Limit Disables or enables the shutdown of the control due to motor overcurrent after 7 seconds High Pedal Disable J4 Non High Pedal Disable High Pedal Disable In HPD the Main Speed Potentiometer needs to be reset to zero before motor is allowed to run Stop Mode J5 Decel Fixed Allows stop function Enable Key Switch Direction Command to use DECEL Trimpo...

Страница 4: ... used to enable power to the control Power On LED will illuminate green to indicate that the Key Switch is activated 3 Main Speed Potentiometer 5 k Ohm 4 The mechanical life of the relay is 10 million cycles The Cycle Jumper J7 is useful for repetitive on off cycling of the control In the OFF position cycling off the relay will engage to brake when a stop command is given In the ON position cyclin...

Страница 5: ...e year it is necessary to recondition the power supply bus capacitors To recondition the bus capacitors apply the DC input voltage with the drive in the Stop Mode for a minimum of one hour Not following this procedure will cause the bus capacitors to fail A40196 Rev A00 8 13 2013 ...