KBAC SERIES INSTALLATION AND OPERATION MANUAL 

15

6 – AC LINE INPUT FUSING 

The drive does not contain line fuses. Most electrical codes require that each ungrounded conductor contain circuit protection. Do not fuse 
neutral or ground connections. It is recommended to install a fuse (Littelfuse 312/314, Buss ABC, or equivalent) or a circuit breaker in series 
with each ungrounded conductor. Do not fuse motor leads. For the recommended fuse size, see Table 2 on page 7. 

 

 

CAUTION! 

Do not fuse neutral or grounded connections. 

 
 
 

7 – ELECTRICAL CONNECTIONS 

Wire the drive in accordance with the National Electrical Code requirements and other local codes that may apply to the application. 

 

 

WARNING!

 Read Safety Warnings, on page 5, before using the drive. Disconnect main power before making connections to the drive.    

To avoid electric shock, be sure to properly ground the drive. It is highly recommended that the Signal Isolator be installed when using signal 
following. 

 

 

WARNING! HIGH VOLTAGE! REMOTE CONNECTIONS OF POTENTIOMETER, SWITCHES, ETC., WILL HAVE WIRING THAT IS AT 

LINE POTENTIAL. IT IS REQUIRED THAT THE SIGNAL ISOLATOR BE INSTALLED FOR REMOTE CONNECTIONS. 

 
Be sure to properly fuse each AC Line conductor that is not at ground potential. Do not fuse neutral or grounded conductors. A separate AC 
Line switch or contactor must be wired as a disconnect so that each ungrounded conductor is opened. For fuse or circuit breaker selection, 
see Table 2 on page 7. Also see Section 6 above. 
 
To maintain the watertight integrity of the drive, be sure to use suitable liquidtight fittings and wiring which are appropriate for the application. 
Liquidtight Fittings Kits are available for all models. See Section 14 on page 23. 
 
The drive is designed with a hinged case so that when the front cover is open, all wiring stays intact. To open the cover, the four screws must 
be loosened so they are no longer engaged in the case bottom. After mounting and wiring, close the cover making sure that the wires do not 
get caught or crimped as the cover is closed. Tighten the four screws so that the gasket is slightly compressed. The recommended tightening 
torque is 12 in-lbs (14 kg-cm) – do not overtighten. See Figures 8 – 10 on pages 12 – 14 for the tightening sequence. 
 

Application Note:

 To avoid erratic operation, do not bundle the AC Line and motor wires with each other or with wires from signal following, 

start/stop contacts, or any other signal wires. Also, do not bundle motor wires from multiple drives in the same conduit. Use shielded cables on 
all signal wiring over 12" (30 cm). The shield should be earth grounded on the drive side only. Wire the drive in accordance with the National 
Electrical Code requirements and other local codes that may apply. 
 

TABLE 4 

TERMINAL BLOCK WIRE SIZE AND TIGHTENING TORQUE SPECIFICATIONS 

Terminal 

Block Description 

Model

Maximum 

Wire Size (Cu) 

Recommended 

Tightening Torque

AWG

mm

2

 in-lbs

kg-cm

TB1 

AC Line Input and 

Motor Wiring 

KBAC-24D 12 

3.3 

KBAC-27D, 29, 29 (1P), 45, 48 

12 

3.3 

12 

14 

TB2 

Run/Fault Relay 
Output Contacts 

KBAC-24D, 27D, 29, 29 (1P), 45, 48 

14 

2.08 

3.5 

KBAC-217, 217S, 217F, 217SF, 416, 416S, 416F, 416SF

12 

3.3 

4.4 

 
 

7.1 – AC LINE INPUT CONNECTION 

Connect the AC Line input to Terminal Block TB1. See Figures 11 – 13 on pages 15 and 16. 
 

GFCI Operation:

 Second Generation (2G) models require custom software – contact Technical Support. Third Generation models are jumper 

selectable (J12) for Standard (G1) or Sensitive (G2) GFCIs. 

 

 

CAUTION!

 The rated AC Line voltage of the drive must match the actual AC Line input voltage. On KBAC-24D, 27D the setting of Jumper 

J1 must match the AC Line input voltage. 
 

KBAC-24D, 27D:

 Designed to accept 1-phase AC Line input only (Terminals 

L1, L2). Rated for 208/230 Volt AC Line input with Jumper J1 set to the "230V" 
position (factory setting). Rated for 115 Volt AC Line input with Jumper J1 set 
to the "115V" position. See Figure 11. 
 

KBAC-29 (1P):

 Designed to accept 1-phase AC Line input (Terminals L1, L2). 

Rated for 208/230 Volt AC Line input only. See Figure 11. 
 
 
 
 
 
 
 
 
 
 
 

FIGURE 11 

KBAC-24D, 27D*, 29 (1P) 

AC LINE INPUT, MOTOR, AND GROUND CONNECTIONS

W

V

U

L1

L2

AC LINE

MOTOR

Содержание KBAC-217

Страница 1: ...2G and 3G Models3 5 KBAC 24D 27D 29 29 1P 45 48 217 217S 217F 217SF 416 416S 416F 416SF The information contained in this manual is intended to be accurate However the manufacturer retains the right to make changes in design which may not be included herein Notes 1 UL approved as an electronic overload protector for motors 2 Special software is available for PSC motors contact Technical Support 3 ...

Страница 2: ...Manual Start Selection J3 19 10 4 Motor Frequency Selection J4 and J5 19 10 4 1 Setting the Drive for 50 Hz or 60 Hz Motor Operation J4 and J5 19 10 4 2 Setting the Drive for Two Times the Rated Motor RPM J4 and J5 19 10 5 Boost Mode Selection J6 20 10 6 Braking Mode Selection J7 20 10 7 Run Fault Output Relay Operation Selection J8 20 10 8 Stop Contact Type Selection J9 20 10 9 Torque Mode Select...

Страница 3: ...lection J10 20 32 Switching Frequency and GFCI Selection Third Generation 3G Drives Only J12 20 33 Minimum Speed Trimpot MIN Range 21 34 Maximum Speed Trimpot MAX Range 21 35 Acceleration Trimpot ACCEL Range 21 36 Deceleration Trimpot DECEL Range 21 37 DC Injection Brake Trimpot DECEL Range 21 38 Slip Compensation Trimpot COMP Range 22 39 Current Limit Trimpot CL Range 22 40 I2 t Trip Time vs Moto...

Страница 4: ...rminals L1 L2 L3 AC Line input Rated for 208 230 Volt AC Line input only Rated for 2 HP maximum with 1 phase AC Line input and 3 HP maximum with 3 phase AC Line input KBAC 217 217S 217F 217SF Designed to accept 3 phase Terminals L1 L2 L3 AC Line input only Rated for 208 230 Volt AC Line input only KBAC 45 48 416 416S 416F 416SF Designed to accept 3 phase Terminals L1 L2 L3 AC Line input only Rated...

Страница 5: ...ntilated 3 phase AC induction motors will overheat if used beyond a limited speed range at full torque Therefore it is necessary to reduce motor load as speed is decreased Note Some fan cooled motors can be used over a wider speed range Consult the motor manufacturer for details CAUTION 1 Some motors have low speed characteristics which cause overheating and winding failure under light load or no ...

Страница 6: ...vided for easy installation of accessories Custom software all models can be factory programmed for applications which require special timing PLC functions and GFCI operation 4 1 STANDARD FEATURES Industrial Duty Die Cast Aluminum Case with Hinged Cover Available in dark gray finish or FDA approved white finish Simple to Operate Does not require programming Uses trimpots and jumpers which are fact...

Страница 7: ...n Specification Factory Setting 115 Volt AC Line Input Voltage Operating Range Volts AC 115 15 208 230 Volt AC Line Input Voltage Operating Range Volts AC 208 15 230 15 400 460 Volt AC Line Input Voltage Operating Range Volts AC 380 15 460 15 Maximum Load Current Overload for 2 Minutes 150 Switching Frequency kHz Jumper J12 3G Drives Only 1 8 12 8 Signal Following Input Voltage Range2 Volts DC 0 5...

Страница 8: ... selection See Section 10 4 on page 19 7 Jumper J12 Switching Frequency and GFCI selection Third Generation 3G drives only See Section 10 11 on page 20 8 Jumper J6 Adjustable Boost selection See Section 10 5 on page 20 9 Jumper J7 Regeneration or DC Injection Braking See Section 10 6 on page 20 10 Jumper J8 Run or Fault Output Relay Operation selection See Section 10 7 on page 20 11 Jumper J9 Norm...

Страница 9: ...per J4 Frequency Multiplier selection See Section 10 4 on page 19 8 Jumper J7 Regeneration or DC Injection Braking See Section 10 6 on page 20 9 Jumper J5 Motor Frequency selection See Section 10 4 on page 19 10 Jumper J8 Run or Fault Output Relay Operation selection See Section 10 7 on page 20 11 Jumper J9 Normally Open or Closed Stop Contact selection See Section 10 8 on page 20 12 Jumper J10 Co...

Страница 10: ...n 10 5 on page 20 7 Jumper J4 Frequency Multiplier selection See Section 10 4 on page 19 8 Jumper J7 Regeneration or DC Injection Braking See Section 10 6 on page 20 9 Jumper J5 Motor Frequency selection See Section 10 4 on page 19 10 Jumper J8 Run or Fault Output Relay Operation selection See Section 10 7 on page 20 11 Jumper J9 Normally Open or Closed Stop Contact selection See Section 10 8 on p...

Страница 11: ...MIN Acceleration ACCEL Deceleration DECEL DC Injection Brake DECEL Boost BOOST Current Limit CL Jog JOG Slip Compensation COMP See Section 12 on pages 21 and 22 8 Selectable Jumpers Motor Horsepower J2 Automatic Ride Through or Manual Start J3 Frequency Multiplier J4 Motor Frequency J5 Fixed or Adjustable Boost J6 Regeneration or DC Injection Braking J7 Run or Fault Output Relay Operation J8 Norma...

Страница 12: ...care should be taken to avoid extreme hazardous locations where physical damage can occur When mounting the drive in an enclosure the enclosure should be large enough to allow for proper heat dissipation so that the ambient temperature does not exceed 40 C 104 F at full rating See Figures 8 10 on pages 12 14 WARNING Do not use this drive in an explosion proof application Be sure the control is sec...

Страница 13: ...KBAC SERIES INSTALLATION AND OPERATION MANUAL 13 FIGURE 9 KBAC 27D 29 29 1P 45 48 MECHANICAL SPECIFICATIONS Inches mm Tighten these screws in the sequence shown to 12 in lbs 14 kg cm ...

Страница 14: ...KBAC SERIES INSTALLATION AND OPERATION MANUAL 14 FIGURE 10 KBAC 217 217S 217F 217SF 416 416S 416F 416SF MECHANICAL SPECIFICATIONS Inches mm ...

Страница 15: ...he cover making sure that the wires do not get caught or crimped as the cover is closed Tighten the four screws so that the gasket is slightly compressed The recommended tightening torque is 12 in lbs 14 kg cm do not overtighten See Figures 8 10 on pages 12 14 for the tightening sequence Application Note To avoid erratic operation do not bundle the AC Line and motor wires with each other or with w...

Страница 16: ...Ground Wire Earth to the Green Ground Screw The Ground Screws are located next to Terminal Block TB1 See Figures 11 13 on pages 15 and 16 7 4 REMOTE MAIN SPEED POTENTIOMETER CONNECTION The drive is supplied with a prewired Main Speed Potentiometer mounted on the front cover To operate the drive from a remote potentiometer 5 kΩ remove the white orange and violet potentiometer leads from Terminals P...

Страница 17: ...tiometer setting when the AC Line is applied 7 7 VOLTAGE FOLLOWING CONNECTIONS An isolated 0 5 Volt DC analog signal input can also be used to control motor speed in lieu of the Main Speed Potentiometer The drive output will linearly follow the analog signal input Wire the signal input positive lead to Terminal P2 and the negative lead to Terminal P1 With external circuitry a 0 10 Volt DC analog s...

Страница 18: ...atic ramping then the hi pot output must be manually increased to the test voltage and then manually reduced to zero This procedure must be followed for each machine to be tested A suggested hi pot tester is Slaughter Model 2550 CAUTION Instantly applying the hi pot voltage will cause irreversible damage to the drive which will void the warranty FIGURE 21 TYPICAL HI POT TEST SETUP AC Line Input 9 ...

Страница 19: ...seconds the drive will shut down and then ride through and automatically return to the set frequency See Figure 24 If Jumper J3 is set to the M position the drive will have to be manually restarted for a momentary power loss using the Start Stop Switch Also see Section 13 2 on page 23 for the Status ST LED indication On KBAC 24D 217 217S 217F 217SF 416 416S 416 416F 416SF Jumper J3 is labeled AUTO...

Страница 20: ...LY Jumper J12 is factory set to the 8K position for a switching frequency at the motor of 8 kHz For 12 kHz switching frequency set Jumper J12 to the 12K position This jumper also allows the drive to be used on standard G1 position or sensitive G2 position GFCIs See Figure 32 Note GFCI operation may increase audible motor noise FIGURE 32 SWITCHING FREQUENCY AND GFCI SELECTION KBAC 24D 27D 29 29 1P ...

Страница 21: ...not exercised The Safety Warnings on page 5 must be read and understood before proceeding 12 1 MINIMUM SPEED TRIMPOT MIN Sets the minimum speed of the motor The MIN Trimpot is factory set to 0 of frequency setting For a higher minimum speed setting rotate the MIN Trimpot clockwise See Figure 33 12 2 MAXIMUM SPEED TRIMPOT MAX Sets the maximum speed of the motor The MAX Trimpot is factory set to 100...

Страница 22: ...tor is properly protected with the I2 t feature it is required that the CL Trimpot be set for 160 of the motor nameplate rated current as described below 12 8 BOOST TRIMPOT BOOST The drive is factory set for Fixed Boost Jumper J6 set to the FIX position When the drive is set for Adjustable Boost Jumper J6 set to the ADJ position the BOOST Trimpot can be used to adjust the amount of boost voltage t...

Страница 23: ...ource and the drive Mounts on the drive s PC board with four snap ins 2G 9600C 9600C 9600C 9600C 9600C 9600C 3G1 8890 8890 8890 8890 8890 8890 8890 Auto Manual Switch Kit When used with the Signal Isolator it selects remote process signal or the Main Speed Potentiometer Mounts on the enclosure cover and is supplied with a switch seal to maintain liquidtight integrity 9481 9481 9481 9481 9481 9481 ...

Страница 24: ...ion and removal inconvenience or consequential damage including injury to any person caused by items of our manufacture or sale Some states do not allow certain exclusions or limitations found in this warranty and therefore they may not apply to you In any event the total liability of KB Electronics Inc under any circumstance shall not exceed the full purchase price of this product Rev 2 2000 COPY...

Отзывы: