Kaysun Prodigy Pro AKAY-P 26 DR9 Скачать руководство пользователя страница 31

Oblique

Rough

Warped

 Page 31 

9. Refrigerant Piping Connection

When connecting refrigerant piping, do not let substances or gases other than the specified refrigerant enter the unit. 

The presence of other gases or substances will lower the unit's capacity, and can cause abnormally high pressure in the 

refrigeration cycle. This can cause explosion and injury..

Note on Pipe Length

The length of refrigerant piping will affect the performance and energy efficiency of the unit. Nominal efficiency is tested 

on units with a pipe length of 5 meters (16.5ft), A minimum pipe run of 3 metres is required to minimise vibration & 

excessive noise.
Refer to the table below for specifications on the maximum length and drop height of piping.

Maximum Length and Drop Height of Refrigerant Piping per Unit Model

Model

Capacity (Btu/h)

Max. Length (m)

Max. Drop Height (m)

R-32 Inverter Split Air Conditioner

<15,000

25

10

 15,000 and < 24,000

30

20

 24,000 and < 36,000

50

25

Connection Instructions - Refrigerant 

Piping

Step 1: Cut pipes

When preparing refrigerant pipes, take extra care to 

cut and flare them properly. This will ensure efficient 

operation and minimize the need for future maintenance.
1.  Measure the distance between the indoor and 

outdoor units.

2.  Using a pipe cutter, cut the pipe a little longer than 

the measured distance.

3.  Make sure that the pipe is cut at a perfect 90º of the 

unit.

DO NOT DEFORM PIPE WHILE 

CUTTING

Be extra careful not to damage, dent, or deform the 

pipe while cutting. This will drastically reduce the 

heating efficiency of the unit.

Содержание Prodigy Pro AKAY-P 26 DR9

Страница 1: ... manual for future reference Please check the applicable models technical data F GAS if any and manufacturer information from the Owner s Manual Product Fiche in the packaging of the outdoor unit European Union products only AKAY P 26 DR9 AKAY P 35 DR9 AKAY P 52 DR9 AKAY P 71 DR9 Prodigy Pro Series INSTALLATION OWNER S MANUAL ...

Страница 2: ...tions 4 Owner s Manual Unit Specifications and Features 8 1 Indoor unit display 8 2 Operating temperature 9 3 Other features 10 4 Setting angle of airflow 11 5 Manual operation without Remote 11 Care and Maintenance 12 Troubleshooting 14 ...

Страница 3: ... cables 25 7 Wrap piping and cables 26 8 Mount indoor unit 27 Outdoor Unit Installation 27 1 Select installation location 27 2 Install drain joint 28 3 Anchor outdoor unit 28 4 Connect signal and power cables 30 Refrigerant Piping Connection 31 A Note on Pipe Length 31 B Connection Instructions Refrigerant Piping 31 1 Cut pipe 31 2 Remove burrs 32 3 Flare pipe ends 32 4 Connect pipes 32 Air Evacua...

Страница 4: ... a burning smell immediately turn off the unit and disconnect the power Call your dealer for instructions to avoid electric shock fire or injury Do not insert fingers rods or other objects into the air inlet or outlet This may cause injury since the fan may be rotating at high speeds Do not use flammable sprays such as hair spray lacquer or paint near the unit This may cause fire or combustion Do ...

Страница 5: ...n cord to power the unit Do not share the electrical outlet with other appliances Improper or insufficient power supply can cause fire or electrical shock The product must be properly grounded at the time of installation or electrical shock may occur For all electrical work follow all local and national wiring standards regulations and the Installation Manual Connect cables tightly and clamp them ...

Страница 6: ...stall the unit within 1 meter 3 feet of any combustible materials 8 Do not install the unit in a location that may be exposed to combustible gas leaks If combustible gas accumulated around the unit it may cause fire 9 Do not turn on the power unti all work has been completed 10 When moving or relocating the air conditioner consult experienced service technicians for disconnection and reinstallatio...

Страница 7: ...alth and is bad for the environment Hazardous substances may leak into the ground water and enter the food chain WARNING for Using R32 Refrigerant When flammable refrigerant are employed appliance shall be stored in a well ventilated area where the room size corresponds to the room area as specifiec for operation For R32 refrigerant models Appliance shall be installed operated and stored in a room...

Страница 8: ...ctive Clean feature is turned on For Inverter split type when Self Clean feature is turned on For fixed speed type when 8ºC heating mode is turned on some units when ECO feature is activated some units when wireless control feature is activated some units Display Code Meanings Air Filter pull up NOTE Different models have different front panel and display window Not all the indicators describing b...

Страница 9: ...mperature ranges certain safety protection features may activate and cause the unit to disable Inverter Split Type FOR OUTDOOR UNITS WITH BASEPAN HEATER OR CRANKCASE HEATER When outside temperature is below 0ºC we strongly recommend keeping the unit plugged in at all time to ensure smooth ongoing performance To further optimize the performance of your unit do the following Keep doors and windows c...

Страница 10: ...ating with hot air to blow dry the evaporator thus preventing the growth of mold and keeping the inside clean When this function is turned on the indoor unit display window appears CL after 20 to 45 minutes the unit will turn off automatically and cancel Active Clean function Breeze Away some units This feature avoids direct air flow blowing on the body and make you feel indulging in silky coolnes...

Страница 11: ... airflow can be set by remote control Please refer to the Remote Control Manual Manual Operation withou remote CAUTION The manual button is intended for testing purposes and emergency operation only Please do not use this function unless the remote control is lost and it is absolutely necessary To restore regular operation use the remote control to activate the unit Unit must be turned off before ...

Страница 12: ...an the front panel This can cause the panel to deform or become discolored Cleaning Your Air Filter A clogged air filter can reduce the coolign efficiency of your unit can also make the air flow irregular and too much noisy so please clean the air filter as often as necessary Once the abnormal noise of air flow is heard please clean the air filter immediately 1 The air filter is on the top of the ...

Страница 13: ...isplay To reset the reminder press the LED button on your remote control 4 times or press the MANUAL CONTROL button 3 times If you don t reset the reminder the CL indicator will flash again when you restart the unit Air Filter Replacement Reminder After 2 880 hours of use the display window on the indoor unit will flash nF This is a reminder to replace your filter After 15 seconds the unit will re...

Страница 14: ...rushing air sound may occur when the louver resets its position A squeaking sound may occur after running the unit in HEAT mode due to expansion and contraction of the unit s plastic parts Both the indoor unit and outdoor unit make noises Low hissing sound during operation This is normal and is caused by refrigerant gas flowing through both indoor and outdoor units Low hissing sound when the syste...

Страница 15: ...r nearest customer service center Provide them with a detailed description of the unit malfunction as well as your model number Troubleshooting When troubles occur please check the following points before contacting a repair company Problem Possible Causes Solution Poor Cooling Performance Temperature setting may be higher than ambient room temperature Lower the temperature setting The heat exchan...

Страница 16: ...ting performance The outdoor temperature is extremely low Use auxiliary heating device Cold air is entering through doors and windows Make sure that all doors and windows are closed during use Low refrigerant due to leak or long term use Check for leaks re seal if necessary and top off refrigerant Indicator lamps continue flashing The unit may stop operation or continue to run safely If the indica...

Страница 17: ...r optional 1 Mounting plate 1 Fixing screw for remote controller holder optional 2 Anchor 5 8 depending on models Small Filter Need to be installed on the back of main air filter by the authorized technician while installing the machine 1 2 depending on models Mounting plate fixing screw 5 8 depending on models Name Shape Quantity pc Connecting pipe assembly Liquid side Ø6 35 1 4 in Parts you must...

Страница 18: ...lation Location Determine Wall Hole Position Attach Mounting Plate Drill Wall Hole Connect Piping Connect Wiring Prepare Drain Hose Wrap Piping and Cable Mount Indoor Unit Page 18 5 Installation Summary Indoor Unit ...

Страница 19: ...itch 1 2 1 Wall Mounting Plate 2 Front Panel 3 Power Cable 4 Louver 5 Air filter pull it out 6 Drainage Pipe 7 Signal Cable 8 Refrigerant Piping 9 Remote Controller 10 Remote Controller Holder Some Units 11 Outdoor Unit Power Cable NOTE ON ILLUSTRATIONS Illustrations in this manual are for explanatory purposes The actual shape of your indoor unit may be slighly different The actual shape shall pre...

Страница 20: ...ective piping step for the signal cable and refrigerant piping that connect the indoor and outdoor units The default position for all piping is the right side of the indoor unit while facing the unit However the unit can accomodate piping to both the left and right Refer to the following diagram to ensure proper distance from walls and ceiling NOTE If no need the back holder to prop up the unit Fi...

Страница 21: ...ole This protects the edges of the hole and will help seal it when you finish the installation process CAUTION When drilling the wall hole make sure to avoid wires plumbing and other sensitive components MOUNTING PLATE DIMENSIONS Different models have different mounting plates For the convenience of installation there are bubble level carved dimensions on the mounting plate Please install the plat...

Страница 22: ...d side piping please make sure that the pipes come out horizontally so as not to affect the lower panel installation CAUTION Be extremely careful not to dent or damage the piping while bending them away from the unit Any dents in the piping will affect the unit s performance If refrigerant piping is already embedded in the wall do the following Step 1 Hook the indoor unit on the mounting plate 1 K...

Страница 23: ... the holder at the back of the unit to prop up the unit giving you enough room to connect the refrigerant piping signal cable and drain hose 5 Connect the indoor unit s refrigerant piping to the connective piping that will join the indoor and outdootr units Refer to the Refrigerant Piping Connection section of this manual for detailed instructions 6 Based on the position of the wall hole relative ...

Страница 24: ... a licensed electrician 2 All electrical connections must be made according to the Electrical Connection Diagram located on the panels of the indoor and outdoor units 3 If there is a serious safety issue with the power supply stop work immediately Explain your reasoning to the client and refuse to install the unit until the safety issue is properly resolved 4 Power voltage should be within 90 110 ...

Страница 25: ...ted on the side panel of the unit Refer to this nameplate to choose the right cable fuse or switch 1 Open and fix the position of the panel then open the covers of the two lock blocks unscrew the screw then hold both sides of the lower panel in the place marked PULL pull it upwards to release the buckles then take the lower panel down please refer to Page 22 23 2 Open the wire box cover to connect...

Страница 26: ...P ENDS OF PIPING When wrapping the bundle keep the ends of the piping unwrapped You need to access them to test for leaks at the end of the installation process refer to Electrical Checks and Leak Checks section of this manual Step 8 Mount indoor unit If you installed new connective piping to the outdoor unit do the following 1 If you have already passed the refrigerant piping through the hole in ...

Страница 27: ...the base pad to prevent ice buildup and coil damage Mount the unit high enough to be above the average accumulated area snowfall The minimum height muse be 18 inches DO NOT install unit in the following locations Near an obstacle that will block air inlets and outlets Near a public street crowded areas or where noise from the unit will disturb others Near animals or plants that will be harmed by h...

Страница 28: ...ber seal see Fig B do the following 1 Insert the drain joint into the hole in the base pan of the unit The drain joint will click in place 2 Connect a drain hose extension not included to the drain joint to redirect water from the unit during heating mode IN COLD CLIMATES In cold climates make sure that the drain hose is as vertical as possible to ensure swift water drainage If water drains too sl...

Страница 29: ...drill holes for expansion bolts 3 Place a nut on the end of each expansion bolt 4 Hammer expansion bolts into the pre drilled holes 5 Remove the nuts from expansion bolts and place outdoor unit on bolts 6 Put washer on each expansion bolt then replace the nuts 7 Using a wrench tighten each nut until snug WARNING WHEN DRILLING INTO CONCRETE EYE PROTECTION IS RECOMMENDED AT ALL TIMES If you will ins...

Страница 30: ... crimp u lugs on the ends of the wires PAY ATTENTION TO LIVE WIRE While crimping wires make sure you clearly distinguish the Live L Wire from other wires WARNING ALL WIRING WORK MUST BE PERFORMED STRICTLY IN ACCORDANCE WITH THE WIRING DIAGRAM LOCATED INSIDE OF WIRE COVER OF THE OUTDOOR UNIT 2 Unscrew the electrical wiring cover and remove it 3 Unscrew the cable clamp below the terminal block and p...

Страница 31: ...fications on the maximum length and drop height of piping Maximum Length and Drop Height of Refrigerant Piping per Unit Model Model Capacity Btu h Max Length m Max Drop Height m R 32 Inverter Split Air Conditioner 15 000 25 10 15 000 and 24 000 30 20 24 000 and 36 000 50 25 Connection Instructions Refrigerant Piping Step 1 Cut pipes When preparing refrigerant pipes take extra care to cut and flare...

Страница 32: ... pipe with insulating material 3 Place flare nuts on both ends of pipe Make sure they are facing in the right direction because you can t put them on or change their direction after flaring 4 Remove PVC tape from ends of pipe when ready to perform flaring work 5 Clamp flare form on the end of the pipe The end of the pipe must extend beyond the edge of the flare form in accordance with the dimensio...

Страница 33: ...0 kgf cm 23 2 23 7 0 91 0 93 DO NOT USE EXCESSIVE TORQUE Excessive force can break the nut or damage the refrigerant piping You must not exceed torque requirements shown in the table above Instructions for Connecting Piping to Outdoor Unit 1 Unscrew the cover from the packed valve on the side of the outdoor unit 2 Remove protective caps from ends of valves 3 Align flared pipe end with each valve a...

Страница 34: ... unit is installed higher than the indoor unit It is recommended that you do not extend the vertical suction Proper oil return to the compressor must be maintained with the speed of the suction gas If the speed is less than 7 62m s the oil return will be reduced One trap should be installed every 6m of vertical suction piping Indoor unit Indoor unit Oil trap Gas pipe Outdoor unit Outdoor unit Gas ...

Страница 35: ... the vacuum pump to evacuate the system 5 Run the vacuum for at least 15 minutes or until the Compound Meter reads 76cmHG 105 Pa 6 Close the Low Pressure side of the manifold gauge and turn off the vacuum pump 7 Wait for 5 minutes then check that there has been no change in system pressure 8 If there is a change in system pressure refer to Gas Leak Check section for information on how to check for...

Страница 36: ...t to be charged can be calculated using the following formula ADDITIONAL REFRIGERANT PER PIPE LENGTH Connective Pipe Length m Air Purging Method Additional Refrigerant Standard pipe length Vacuum Pump N A Standard pipe length Vacuum Pump Liquid Side Ø 6 35 Ø0 25 R 32 Pipe length standard length x 12g m Pipe length standard length x 0 13 oZ ft Liquid Side Ø 9 52 Ø0 375 R 32 Pipe length standard len...

Страница 37: ...ing resistance tester Grounding resistance must be less than 0 1Ω DURING TEST RUN Check for Electrical Leakage During the Test Run use an electroprobe and multimeter to perform a comprehensive electrical leakage test If electrical leakage is detected turn off the unit immediately and call a licensed electrician to find and resolve the cause of the leakage WARNING RISK OF ELECTRIC SHOCK ALL WIRING ...

Страница 38: ...E CHECK PIPE CONNECTIONS During operation the pressure of the refrigerant circuit will increase This may reveal leaks that were not present during your initial leak check Take time during the Test Run to double check that all refrigerant pipe connection points do not have leaks Refer to Gas Leak Check section for instructions 5 After the Test Run is successfully completed and you confirm that all ...

Страница 39: ...hange without prior notice for product improvement Consult with the sales agency or manufacturer for details Any updates to the manual will be uploaded to the service website please check for the latest version CS014UI EP B 16122000009397 20200428 ...

Страница 40: ......

Страница 41: ......

Отзывы: