Reference table of R410A indoor unit connecting pipe 

Dimensions of connecting pipe diameters in accessory 

Table 5-4  

Flare(connecting to 
gas side stop valve) 

Main pipe dimensions  

Downstream indoor  
 unit capacity      

Applicable   
manifolds  

Gas pipe 

Φ15.9  

Φ19.1 

Φ22.2 

Φ25.4 

Φ25.4 

Liquid pipe  

Φ9.5  

A

166  

166≤A

230  

230≤A

330  

330≤A

460  

460≤A  

FQZHN-01C  

FQZHN-01C  

FQZHN-02C  

FQZHN-02C  

FQZHN-02C  

Φ9.5  

Accessory- 
connecting pipe 

Φ9.5  

Φ12.7  

Φ12.7  

Φ22.2 

5.4  Diameters of outdoor unit connecting pipe 

Reference table of R410A outdoor unit connecting pipe 

Table 5-5  

Main pipe dimensions when  
equivalent length of liquid side  
and gas side pipe is 

90m 

Main pipe dimensions when  
equivalent length of liquid side  
and gas side pipe is ≥90m 

Connect this end to the   
connecting pipe in accessory  

Outdoor unit   
capacity  

Gas sideLLiquid side  Indoor unit   Gas side   Liquid side   Indoor unit   

(mm)   

(mm)   first manifold   (mm)   

(mm)   first manifold  

Accessory-connecting to elbow  

Φ22.2 

40kW  

Φ22.2 

Φ12.7 

FQZHN-02C  Φ25.4 

Φ12.7 

FQZHN-02C 

45kW  

Φ25.4 

Φ12.7 

FQZHN-02C  Φ28.6 

Φ12.7 

FQZHN-03C 

CAUTION 

The horizontal straight pipe distance between angle branch  and  
its adjacent manifold should be at least 0.5m  

Connect this end   
to the main pipe  

The horizontal straight pipe distance between 2 adjacent 2  
manifold should be at least 0.5m   

The horizontal straight pipe distance that connets to indoor unit  
behind the manifold should be at least 0.5m  

Elbow connecting instruction  

Main pipe diameters  
of connecting pipes 

Connecting pipe bending process  

Use the maximum indoor and outdoor connecting pipe diameter. 

Cut the pipe at A,  insert the main pipe  
and weld 

Φ22.2 

Joint dimension 

Cut the pipe at A, flare and weld  

Φ25.4 

Φ28.6 

Table 5-6  

Pipe diameters of the indoor unit joint 

Insert main pipe directly and weld 

Refrigerant  

Model  

Gas side  

Liquid side  

Wall mounting 22~45 

Wall mounting 56 

Φ12.7(Flare) 

Φ15.9(Flare) 

Φ12.7(Flare) 

Φ15.9(Flare) 

Φ12.7(Flare) 

Φ15.9(Flare) 

Φ12.7(Flare) 

Φ15.9(Flare) 

Φ15.9(Flare) 

Φ12.7(Flare) 

Φ15.9(Flare) 

Φ15.9(Flare) 

Φ6.4(Flare) 

Φ9.5(Flare) 

Φ6.4(Flare) 

Φ9.5(Flare) 

Φ6.4(Flare) 

Φ9.5(Flare) 

Φ6.4(Flare) 

Φ9.5(Flare) 

Φ9.5(Flare) 

Φ6.4(Flare) 

Φ9.5(Flare) 

Φ9.5(Flare) 

Table 4-8  

Outdoor Unit 

(kW) 

Capacity of  

Outdoor unit (kW)  

of Indoor unit 

Maximum Quantity   Sum Capacity  

of Indoor unit  

Four-side air outlet 28~45 

Four-side air outlet 56~80 

Single-side air outlet 18~45 

Single-side air outlet 56 

Low static pressure 18~45 

Low static pressure 56 

Thin duct 71 

40 kW 

40 

35 

39 

150% 

150% 

R410A 

45kW 

45 

CAUTION 

A5 Duct 22~45 

Capacity of indoor unit shouldn’t be greater than the sum of 150%  

A5 Duct 56~80 

of outdoor unit loading. 

A5 Duct 90~140 

When running with oversized bearings,  attenuation will happen  
correspondingly. 

Pipe diameters of the outdoor unit joint  

Table 5-7   

Table 5-9  

To pipe side   

Pipe diameters of the outdoor unit joint  

Classification   

Gas side  

Φ22.2 

Liquid side  

of power  

22  

0.8  

80  

3  

28  

36  

1.2  

100  

3.7  

45  

1.7  

112  

4  

56  

2  

71  

2.5  

140  

5  

Model 

40kW 

HP 

Φ12.7 

Classification   
of power  

45kW 

Φ25.4 

90  

3.2  

125  

4.5  

HP 

installation manual 

Содержание KMF-400 DN3

Страница 1: ...ou very much for purchasing our air conditioner Before using your air conditioner please read this manual carefully and keep it for future reference INSTALLATION MANUAL Amazon Unitario KMF 400 DN3 KMF 450 DN3 ...

Страница 2: ...refrigerant gas doer not leak CAUTION New Refrigerant Air Conditioner Installation THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT R410A WHICH DOES NOT DESTROY OZONE LAYER The characteristics of R410A refrigerant are Hydrophilic oxid izing membrane or oil and its pressure is approx 1 6 times high er than that of refrigerant R22 Accompanied with the new refrig erant refrigerating oil has also b...

Страница 3: ...gth of indoor outdoor unit liquid side pipes 2 Mark refrigerant adding amount pipe diameters of pipe length actual length and height difference between indoor and outdoor unit on the usage confirm form of outdoor unit on electronic control box plate in advance in order to further use 3 2 Refrigerant pipe 1 Use the central air conditioner specified refrigerant pipe 2 Refrigerant pipe with specified...

Страница 4: ...tion of the machine may be caused Fig 4 4 There is combustible gas leakage 4 2 Handling There is much oil including engine oil ingredient There is salty air surrounding near the coast 1 Do not unpacking the unit when handling Use two ropes whose lengths are more than 8m to handle the unit Keep balance of the unit when lifting stably Use a padding plate or packing materials for protection if the pa...

Страница 5: ...act symmetrically Fig 4 8 Ensure the the basement supports the vertical foldings of the front and back bottom plates directly since its the actual bearing place Macadam base is unnecessary But cocrete surface should be roughed The proportions used in mixing the concrete should be cement 1 sand 2 pebble 4 including Φ10reinforced rebar Even the surface of concrete The edge of the basement should be ...

Страница 6: ... d L4 L5 The first manifold D E N4 C Fig 5 2 Table 5 2 e f N5 N6 Tightening torque Pipe dimensions N m Fig 5 4 14 2 17 2 N m 144 176 kgf cm φ6 4 32 7 39 9 N m 333 407 kgf cm CAUTION φ9 5 49 5 60 3 N m 504 616 kgf cm All the manifolds used should be specialized ones designated by our company Fail to follow the requirements could lead to system error φ12 7 61 8 75 4 N m 630 770 kgf cm φ15 9 If the d...

Страница 7: ...0 5m Elbow connecting instruction Main pipe diameters of connecting pipes Connecting pipe bending process Use the maximum indoor and outdoor connecting pipe diameter Cut the pipe at A insert the main pipe and weld Φ22 2 Joint dimension Cut the pipe at A flare and weld Φ25 4 Φ28 6 Table 5 6 Pipe diameters of the indoor unit joint Insert main pipe directly and weld Refrigerant Model Gas side Liquid ...

Страница 8: ... maximum principle adopt Φ28 6 Φ12 7 Fig 5 5 CAUTION Suppose in the displayed piping system the total equivalent piping length of air side liquid side is longer than 90m Connecting method Table 5 10 Gas side Liquid side Flare welding Flare welding 1 Indoor unit branch pipe Outdoor unit 40kW Outdoor unit 45kW Flare welding Flare welding Inner branch pipes are a f the size selection please refers to...

Страница 9: ...sure there is no any dirt or water before connecting the pipe to the outdoor units Liquid side stop valve Gas side stop valve 2 Wash the pipe with high pressure nitrogen never use refrigerant of outdoor unit 5 7 Airtight Test 1 Connect the high pressure side pipe and liquid side stop valve after connecting indoor unit pipes Nitrogen Nitrogen Liquid pipe Gas pipe Meter connector components used for...

Страница 10: ... side Fig 5 9 Fig 5 11 5 10 Leakage inspection Inspect each joint to check if it leaks by using a leak detector CAUTION or suds Fig 5 12 Do not mixedly use tools used for different refriferant tools and measuring instrument that directly contact refriferant DO NOT use refriferant gas to air discharge NOTE A liquid side stop valve B gas side stop valve C and D are the joint of the indoor unit conne...

Страница 11: ...refrigerant should be added in liquid quantifiedly by electronic scale 5 13 Manifold installation key points Install it in a horizonal level error angle should less than 10 It may result in damage if installing in a wrong way 6 2 Indoor unit system wiring 1 Individual power supply without power supply device See the table below Table 6 1 Fig 5 14 CAUTION Wiring diameters and continuous lengths in ...

Страница 12: ...6 3 Outdoor unit main control board Fig 6 3 installation manual 11 ...

Страница 13: ... Loading output terminal EXV A driving port Reserved Control port of DC fan A EXV B driving port Loading output terminal Control port of DC fan B Current inspection port of the inverter compressor A and B Loading output terminal Loading output terminal Power supply connected port of the main control panel Power output of the No 1 transformer 6 5 Dial indication sign instructions ENC3 and S12 defin...

Страница 14: ...CCB and manual switch Cooling priority mode 3 Power supply RCCB and manual switch used for a same indoor unit should have universality Indoor unit power supply for the same unit should use the same circuit and ON OFF simultaneously or it could seriously affect the system service life and the unit may fail to power on Number 63 the more operating mode first Only respond the heating mode 4 Consider ...

Страница 15: ...copressor and other components PQE connects to weak current signal wire don t connect it to strong current All the connecting terminal should be fastened reliably ground wire should be grounded correctly Use wiring terminal power supply wire with a torus After power supply wire has been connected to the wiring base it needs to be reliably fastened Power on after a careful inspection and make sure ...

Страница 16: ...ant critical thickness 0 44 kg m3 for R410A Outdoor unit Indoor unit Room full of leak refrigerant All refrigerant has run up Confirm the critical thickness through follow steps and take necessary actions 1 Calculate the sum of the charge volume A kg Total refrigerant volume of 10HP factory refrigerant volume super addition 2 Calculate the indoor cubage B m as the minimum cubage 3 Calculate the re...

Страница 17: ... normal If there s vibration and abnormal noise when operating Test if heating function works normally for heating and cooling A C 2 Outdoor unit If there s vibration and abnormal noise when operating Whether the wind and noise and condenser water could influence your neighbour If there s refrigerant leakage CAUTION When electrified start the unit immediately or reboot after shutdown A C has prote...

Страница 18: ......

Страница 19: ...ch having a contact separation of at least 3mm in all poles should be connected in fixed wiring The appliance shall be installed in accordance with national wiring regulations The temperature of refrigerant circuit will be high please keep the interconnection cable away from the copper tube The power cord type designation is H05RN R or above H07RN F MD13I 052CW DZD 16127000A03538 ...

Страница 20: ......

Отзывы: