16 CN33: COMP-STATE,connect with an ac light to indicate the state of the compressor
Attention: the control port value of the pump actually detected is ON/OFF but not 220-230V control power supply, so
special attention should be paid when installing the light.
17 CN2: HEAT1. Pipeline Auxiliary Heater
Attention: the control port value of the pump actually detected is ON/OFF but not 220-230V control power supply, so
special attention should be paid when installing the pipeline auxiliary heater.
18 CN24: The alarm signal output of the unit(ON/OFF signal)
Attention: the control port value of the pump actually detected is ON/OFF but not 220-230V control power supply, so
special attention should be paid when installing the alarm signal output.
19 CN20: TP-PRO, Discharge temperature switch protection (protection code P0, provent the compressor from over
temperature 115ºC)
20 CN71: EXVB, System electronic expansion valve2. Used for cooling.
21 CN72: WXVC, EVI electronic expansion valve. Used for EVI.
22 CN70: EXVA, System electronic expansion valve1.
23 CN60: Outdoor units communication or HMI conmunication port
24 CN61: Outdoor units communication or HMI conmunication port
25 CN64: Fan inverter module communication ports
26 CN65: Compressor inverter module communication ports
27 CN300: Program burn in port (WizPro200RS programming device).
28 IC10: EEPROM chip
29 CN1: temperature sensors input port.
T4: outdoor ambient temperature sensor
T3A/T3B: pipe temperature sensor of the condenser
T5: wtater tank temperature sensor
T6A: Refrigerant inlet temperature of EVI plate heat exchanger
T6B: Refrigerant inlet temperature of EVI plate heat exchanger
30 CN16: System pressure sensor
31 CN31: Temperature sensors input port
Th: System suction temperature sensor
Taf2: Water side antifreeze temperature sensor
Two: Unit water outlet temperature sensor
Twi: Unit water inlet temperature sensor
Tw: Total water outlet temperature sensor when several units are connected in parallel
32 CN69: Temperature sensors input port
Tp1: DC inverter compressor 1 discharge temperature sensor
Tp2: DC inverter compressor 2 discharge temperature sensor
Tz/7: coil final outlet temperature sensor
Taf1: Water side antifreeze temperature
33 CN19: Low voltage protection switch. (Protection code P1)
34 CN91: Three-phase protector output switch. (Protection code E8)
35 CN58: Fan realy driver port.
36 CN8: Remote function of cool/heat signal
37 CN8: Remote function of on/off signal
38 CN8: Water flow switch signal
39 SW3: Up button
a) Select different menus when enter menu selection.
b) For sopt inspection in conditions.
SW4: Down button
a) Select different menus when enter menu selection.
b) For sopt inspection in conditions.
SW5: Menu button
Press to enter menu selection, short press to return to the previous menu.
SW6: OK button
Enter the submenu or confirm the function selected by short pressing.
40 CN18: Program burn in port (USB).