01
ACCESSORIES
Unit
Installation
& Operation Manual
Water Temperature
Sensor
ErP
Information
Temperature testing
components of total
water outlet
Transformer
Installation manual of
wired controller
Quantity
1
2
1
1
1
1
Shape
/
/
Purpose
/
/
/
Use for installation (only need for setting the main module)
1 INTRODUCTION
1.1 Use conditions of the unit
1) The standard voltage of power supply is 380-415V 3N~50Hz, the minimum allowable voltage is 342V, and the maximum
voltage is 456V.
2) To maintain better performance, please operate the unit under the following outdoor temperature:
-25
-20
-15
-10
-5
0
5
10
15
20
25
30
35
40
45
50
20
25
30
35
40
45
50
55
60
-15
-10
-5
0
5
10
15
20
25
30
35
40
45
50
55
0
5
10
15
20
25
30
G
KEM-30 DRS4.1 KH & KEM-60 DRS4.1 KH
KEM-90 DRS4 KH
KEM-30 DRS4.1 KH & KEM-60 DRS4.1 KH
Fig. 1-1-1 Cooling operating range
Outlet water temperature (°C)
COOLING
HEATING
Outlet water temperature (°C)
Two [°C]
Two [°C]
Outlet water temperature (°C)
Outlet water temperature (°C)
Fig. 1-1-2 Heating operating range
Fig. 1-2-1 Cooling operating range
Fig. 1-2-2 Heating operating range
Ambient temperature (°C)
In cooling mode, the minimum water output of 0C can be set (the units(KEM-30 DRS4.1 KH&KEM-60 DRS4.1 KH) can
be set through the main control board dial code S12-3, and the unit(KEM-90 DRS4 KH) can be set through the service menu
of the wire controller ). When the set temperature is less than 5 degrees, the water side system must add antifreeze Liquid
(concentration above 15%), otherwise the unit will be damaged.
Ambient temperature (°C)
T4 [°C]
T4 [°C]
KEM-90 DRS4 KH