background image

 Page 14 

Issue

Possible Causes

The outdoor unit makes 

noises

The unit will make different sounds based on its current operating mode.

The outdoor unit makes 

noises

The unit may accumulate dust during extended periods of non-use, which will be 

emitted when the unit is turned on. This can be mitigated by covering the unit during 

long periods of inactivity

The unit emits a bad odor

The unit may absorb odors from the environment (such as furniture, cooking, 

cigarettes, etc.) which will be emitted during operations.

The unit's filters have become moldy and should be cleaned.

The fan of the outdoor unit 

does not operate

The unit's filters have become moldy and should be cleaned.

Operation is erratic, 

unpredictable, or unit is 

unresponsive

Interference from cell phone towers and remote boosters may cause the unit to 

malfunction.

In this case, try the following:
•  Disconnect the power, then reconnect.
•  Press ON/OFF button on remote control to restart operation

NOTE: I

f problem persists, contact a local dealer or your nearest customer service center. Provide them with a detailed 

description of the unit malfunction as well as your model number.

Troubleshooting

When troubles occur, please check the following points before contacting a repair company.

Problem

Possible Causes

Solution

Poor Cooling 

Performance

Temperature setting may be higher 

than ambient room temperature.

Lower the temperature setting.

The heat exchanger on the indoor or 

outdoor unit is dirty.

Clean the affected heat exchanger.

The air filter is dirty.

Remove the filter and clean it according to instructions.

The air inlet or outlet of either unit is 

blocked.

Turn the unit off, remove the obstruction and turn it back 

on.

Doors and windows are open.

Make sure that all doors and windows are closed while 

operating the unit.

Excessive heat is generated by 

sunlight.

Close windows and curtains during periods of high heat 

or bright sunrise.

Too many sources of heat in the room 

(people, computers, electronics, etc.) Reduce amount of heat sources.

Low refrigerant due to leak or long-

term use.

Check for leaks, re-seal if necessary and top off refrigerant.

SILENCE function is activated 

(optional function)

SILENCE function can lower product performance by 

reducing operating frequency. Turn off SILENCE function.

Содержание CASUAL Series

Страница 1: ...applicable models technical data F GAS if any and manufacturer information from the Owner s Manual Product Fiche in the packaging of the outdoor unit KAY CF 26 DR9 KAY CF 35 DR9 KAY CF 52 DR8 KAY CF 7...

Страница 2: ...ns 4 Owner s Manual 1 Unit Specifications and Features 7 1 Indoor unit display 7 2 Operating temperature 8 3 Other features 8 4 Setting angle of airflow 9 5 Manual operation without Remote 10 2 Care a...

Страница 3: ...7 Wrap piping and cables 22 8 Mount indoor unit 23 8 Outdoor Unit Installation 24 1 Select installation location 24 2 Install drain joint 24 3 Anchor outdoor unit 25 4 Connect signal and power cables...

Страница 4: ...in places near or around combustible gases Emitted gas may collect around the unit and cause explosion Do not operate your air conditioner in a wet room such as a bathroom or laundry room Too much ex...

Страница 5: ...E NOTE OF FUSE SPECIFICATIONS The air conditioner s circuit board PCB is designed with a fuse to provide overcurrent protection The specifications of the fuse are printed on the circuit board such as...

Страница 6: ...aging of the outdoor unit 2 Installation service maintenance and repair of this unit must be performed by a certified technician 3 Product uninstallation and recycling must be performed by a certified...

Страница 7: ...R ON is set FRESH SWING TURBO or SILENCE feature is turned on OF for 3 seconds when TIMER OFF is set FRESH SWING TURBO or SILENCE feature is turned off cF when anti cold air feature is turned on dF wh...

Страница 8: ...low 0 C 32 F we strongly recommend keeping the unit plugged in at all time to ensure smooth ongoing performance NOTE Room relative humidity less than 80 If the air conditioner operates in excess of th...

Страница 9: ...ill increase the temperature by 1 C 2 F after 1 hour and will increase an additional 1 C 2 F after another hour When in HEAT mode the unit will decrease the temperature by 1 C 2 F after 1 hour and wil...

Страница 10: ...To restore regular operation use the remote control to activate the unit Unit must be turned off before manual To operate your unit manually 1 Locate the MANUAL CONTROL button on the right hand side o...

Страница 11: ...r Air Filter A clogged air conditioner can reduce the cooling efficiency of your unit and can also be bad for your health Make sure to clean the filter once every two weeks 1 Lift the front panel of t...

Страница 12: ...isplay To reset the reminder press the LED button on your remote control 4 times or press the MANUAL CONTROL button 3 times If you don t reset the reminder the CL indicator will flash again when you r...

Страница 13: ...rushing air sound may occur when the louver resets its position A squeaking sound may occur after running the unit in HEAT mode due to expansion and contraction of the unit s plastic parts Both the i...

Страница 14: ...rvice center Provide them with a detailed description of the unit malfunction as well as your model number Troubleshooting When troubles occur please check the following points before contacting a rep...

Страница 15: ...ating performance The voltage is too high or too low Install a manostat to regulate the voltage Cold air entering through doors and windows Make sure that all doors and windows are closed during use C...

Страница 16: ...holder optional 1 Mounting plate 1 Fixing screw for remote controller holder optional 2 Anchor 5 8 dependinf on model Small Filter Need to be installed on the back of main air filter by the authorized...

Страница 17: ...ation Location Determine Wall Hole Position Attach Mounting Plate Drill Wall Hole Connect Piping Connect Wiring Prepare Drain Hose Wrap Piping and Cable Mount Indoor Unit Page 17 5 Installation Summar...

Страница 18: ...ounting Plate 2 Front Panel 3 Power Cable Some Units 4 Louver 5 Functional Filter On Back of Main Filter Some Units 6 Drainage Pipe 7 Signal Cable 8 Refrigerant 9 Remote Controller 10 Remote Controlle...

Страница 19: ...cable and refrigerant piping that connect the infoor and outdoor units The default position for all piping is the right side of the indoor unit while facing the unit However the unit can accomodate p...

Страница 20: ...t the unit 2 If the wall hole is behind the unit keep the knock out panel in place If the wall hole is to the side of the indoor unit remove the plastic knock out panel from that side of the unit This...

Страница 21: ...ower supply stop work immediately Explain your reasoning to the client and refuse to install the unit until the safety issue is properly resolved 4 Power voltage should be within 90 110 of rated volta...

Страница 22: ...he unit remove the plastic panel on the bottom left hand side 5 Feed the signal wire through this slot from the back of the unit to the front 6 Facing the front of the unit connect the wire according...

Страница 23: ...the unit The unit should not jiggle or shift 6 Using even pressure push down on the bottom half of the unit Keep pushing down until the unit snaps onto the hooks along the bottom of the mounting plate...

Страница 24: ...ion that is exposed to large amounts of dust In a location exposed to a excessive amounts of salty SPECIAL CONSIDERATIONS FOR EXTREME WEATHER If the unit is exposed to heavy wind Install unit so that...

Страница 25: ...ation base of the unit according to the dimensions below Outdoor Unit Dimensions mm Mounting Dimensions A x H x F Distance A mm Distance B mm 681 x 434 x 285 26 8 x 17 1 x 11 2 460 18 1 292 11 5 700 x...

Страница 26: ...on the inside of the wiring cover WARNING BEFORE PERFORMING ANY ELECTRICAL OR WIRING WORK TURN OFF THE MAIN POWER TO THE SYSTEM 1 Prepare the cable for connection USE THE RIGHT CABLE Indoor Power Cab...

Страница 27: ...frigerant pipes take extra care to cut and flare them properly This will ensure efficient operation and minimize the need for future maintenance 1 Measure the distance between the indoor and outdoor u...

Страница 28: ...is fully flared 8 Remove the flaring tool and flare form then inspect the end of the pipe for cracks and even flaring Step 4 Connect pipes When connecting refrigerant pipes be careful not to use exce...

Страница 29: ...the table above Instructions for Connecting Piping to Outdoor Unit 1 Unscrew the cover from the packed valve on the side of the outdoor unit 2 Remove protective caps from ends of valves 3 Align flared...

Страница 30: ...r at least 15 minutes or until the Compound Meter reads 76cmHG 105Pa del sistema 6 Close the Low Pressure side of the manifold gauge and turn off the vacuum pump 7 Wait for 5 minutes then check that t...

Страница 31: ...outdoor unit s low pressure valve The additional refrigerant to be charged can be calculated using the following formula ADDITIONAL REFRIGERANT PER PIPE LENGTH Connective Pipe Length m Air Purging Met...

Страница 32: ...resistance tester Grounding resistance must be less than 0 1 DURING TEST RUN Check for Electrical Leakage During the Test Run use an electroprobe and multimeter to perform a comprehensive electrical...

Страница 33: ...CONNECTIONS During operation the pressure of the refrigerant circuit will increase This may reveal leaks that were not present during your initial leak check Take time during the Test Run to double ch...

Страница 34: ...ange without prior notice for product improvement Consult with the sales agency or manufacturer for details Any updates to the manual will be uploaded to the service website please check for the lates...

Страница 35: ......

Страница 36: ......

Отзывы: