Amazon V
Part 1 - Gener
al In
forma
tion
13
Table 1-6.5: Extract from Table 1-5.2 Combinations of Indoor and outdoor units
Outdoor unit capacity
Sum of capacity indexes of
connected indoor units (standard
indoor units only)
Maximum number of
connected indoor units
kW
HP
Capacity
index
50.0 18
500
250 to 750
29
56.0 20
560
280 to 840
33
59.0 22
590
295 to 885
36
67.0 24
670
335 to 1005
39
73.0 26
730
365 to 1095
43
75.5 28
755
392.5 to 1132.5
46
85.0 30
850
425 to 1275
50
85.0 32
850
425 to 1275
53
92.5 34
925
462.5 to 1387.5
56
99.0 36
990
495 to 1485
59
104.0 38
1040
520 to 1560
63
109.0 40
1090
545 to 1635
64
115.0 42
1150
575 to 1725
118.0 44
1180
590 to 1770
126.0 46
1260
630 to 1890
132.0 48
1320
660 to 1980
134.5 50
1345
672.5 to 2017.5
146.0 52
1460
730 to 2190
▪
The number of connected indoor units is 8 and the maximum number of connected indoor units on the 20HP outdoor
unit is 33, so the number of connected indoor units is within the limitation.
▪
Calculate the corrected capacity of the outdoor units:
a) The sum of the indoor unit CIs is706 andthe CI of the 20HP outdoor unit (K2F-560 DN5S)is 560, so the combination
ratio is 706 / 560 = 126%.
b) Using the outdoor units’cooling capacity table, interpolate to obtain the capacity (“B”) corrected for outdoor air
temperature, indoorair temperature, and combination ratio.Refer to Tables 1-6.6 and 1-6.7.
Table 1-6.6: Extract from Table 2-8.7 K2F-560 DN5S cooling
capacity
Table 1-6.7: Cooling capacity calculated by interpolation
CR
Outdoor
air temp.
(°C DB)
Indoor air temp.
(°C DB / °C WB)
CR
Outdoor
air temp.
(°C DB)
Indoor air temp.
(°C DB / °C WB)
25.8 / 18.0
25.8 / 18.0
TC
PI
TC
PI
kW
kW
kW
kW
130%
31
60.0
14.25
130%
33
59.2
14.77
33
59.2
14.77
35
58.2
15.32
B = 58.8
1
120%
31
59.0
14.16
120%
33
58.2
14.69
33
58.2
14.69
35
57.2
15.22
Notes:
1. 58.2 + (59.2 – 58.2) × (126 – 120) / (130 – 120) = 58.8.