MALFUNCTION
Malfunction display of outdoor unit’s DSP1
Table.5-1
No.
Error code
Error or protection type
Note
1
E0
Outdoor unit COMM.Error
Only display in slave unit
2
E1
Phase protection
3
E2
COMM.Error with indoor unit
Twenty minutes after the first power on or indoor
and outdoor communication break off after 2
minutes when the unit has been running for 20 minutes
4
E3
Reserve
5
E4
Outdoor temp. sensor error
6
E5
Voltage protection
7
E6
Reserve
8
E7
Discharge temp.sensor error
9
E8
Outdoor unit address error
10
xE9
Mismatching the drive model
X represents for a system, 1 is A system, 2 is B system
11
xH0
COMM. Error between IR341 and main chip
12
H1
COMM. Error between 0537 and main chip
13
H2
Qty.of outdoor unit decreases error
Only main unit will display
14
H3
Qty.of outdoor unit increases error
Only main unit will display
15
xH4
unrecoverable module protection outage(P6)
X represents for a system, 1 is A system, 2 is B
system, not recoverable until re-power on
16
H5
Three times the P2 protection in 60 minutes
Not recoverable until re-power on
17
H6
Three times the P4 protection in 100 minutes
Not recoverable until re-power on
18
H7
Qty.of indoor units decreases error
Indoor unit lost for over 3 minutes; not recoverable,
until the unit qty. recovers
19
H8
High-pressure sensor error
Air discharging pressure Pc≤0.3MPa
20
H9
Three times the P9 protection in 60 minutes
Not recoverable until re-power on
21
Hc
Reserve
22
F0
Three times the PP protection in 150 minutes
Not recoverable until re-power on
23
xF1
DC bus voltage Error
X represents the system, 1 is A system, 2 is B system
DC bus voltage continues for 10s beyond 300-800V.
24
C7
Three times the PL protection in 100 minutes
Not recoverable until re-power on
25
yHd
Auxiliary unit error
(
y=1,2, 3.e.g,1Hd stands for auxiliary
unit1 error
)
Y represents a unit which is not No. 0
26
P0
Inverter compressor top Temp.protection
27
P1
High-pressure protection
28
P2
Low-pressure protection
Reports H5 after P2 protection is activated three times 60 minutes
29
xP3
Compressor current protection
X represents for a system, 1 is A system, 2 is B system
30
P4
Discharge Temp.Protection
Reports H6 after P6 protection is activated three times 100 minutes
31
P5
High condenser Temp.protection
32
xP6
Inverter module protection
X represents for a system, 1 is A system, 2 is B system;
reports H4 if P6 protection is activated three times
60 minutes
33
P9
DC fan protection
Reports H9 if P9 protection is activated three times in 60 minutes
34
PL
Inverter module Temp.sensor error
Reports C7 if PL protection is activated in 100 minutes.
35
PP
Protection at an insufficient degree against superheating
compressor discharge
Reports F0 if PP protection is activated in 150 minutes
36
xL0
DC compressor module error
X represents the system, 1 is A system, 2 is B system
37
xL1
DC bus low-pressure protection
X represents the system, 1 is A system, 2 is B system
38
xL2
DC bus high-pressure protection
X represents the system, 1 is A system, 2 is B system
39
xL3
Reserve
X represents the system, 1 is A system, 2 is B system
40
xL4
MCE error/synchronization/closed loop
X represents the system, 1 is A system, 2 is B system
41
xL5
Zero-speed protection
X represents the system, 1 is A system, 2 is B system
42
xL6
Reserve
X represents the system, 1 is A system, 2 is B system
43
xL7
Phase-error protection
X represents the system, 1 is A system, 2 is B system
44
xL8
Protection of the speed change between a moment
before and after is
>
15Hz
X represents the system, 1 is A system, 2 is B system
45
xL9
Protection of the speed change between the setting
speed and the actual speed
>
15Hz
X represents the system, 1 is A system, 2 is B system
If the problem still exists, please contact the sales distributor or the service center, tell us your model No. and the detail of the error.