    Safety instructions are intended to protect users from dangerous situations and/or 
prevent material damage. In the operating instructions, the severity of the potential risk can 
be indicated by the following signal words:

install

Switches should only be installed in systems that do not exceed the maximum 
pressure Pmax (see type label).Install switches only when power is off 
(electrical, hydraulic/pneumatic).

!

danger

Vibration and violent vibration must be avoided during transportation. 
Even if the switch housing is not damaged,

Internal components can also break down and cause failure.

!

caution

Analog quantity 4-20mA

brown

black

blue

white

1

2

3

4

F mA(flow)

T mA(temperature)

18-28VDC +

-

1

2

3

4

brown

black

blue

white

Power

Temperature analog quantity

Power supply -

Flow analog

FTS520 Wiring diagram

Содержание FTS500 Series

Страница 1: ...Operating instruction Integrated flow and temperature sensor FTS500 FTS520 series Sensor and controller Flow pressure temperature level position...

Страница 2: ...mply may result in fatal injury danger An identifiable hazard Failure to comply may result in fatal injury and damage to equipment or plant parts warning It means a danger Failure to comply may result...

Страница 3: ...0 65 Medium temperature 20 100 Process connection Thread type G3 8 G2 Power supply 18 30VDC Digital display OLED LCD screen 1 1 2 Linearization 5 point linear flow curve Alarm contact 2 independent al...

Страница 4: ...light Flow indicator Instantaneous flow value Signal alarm lamp Signal alarm lamp Flow L min TEMP 30 8 0 0 Flow unit Real time temperature value right increment key FTS500 Liquid crystal display FTS50...

Страница 5: ...2 1 1 0 2 1 6 0 1 6 B 1 2 0 4 0 A 1 2 5 4 0 0 4 0 B 3 4 1 0 0 A 3 4 1 0 1 0 0 1 0 0 B 1 2 5 0 A 1 1 4 5 8 5 8 3 2 3 1 1 1 4 5 0 2 5 0 2 5 0 B 1 1 2 41 5 G G G 15 0 15 0 50 0 L 6 0 M12 1 Aviation plug...

Страница 6: ...bit joint hexagon flow range process connection A B C H L E ES L min R G 004A 25mm 15mm 24mm 30 30m m 80mm 17mm 27mm 0 5 4 3 8 004B 1 2 016A 25mm 15mm 24mm 30 30m m 84mm 19mm 27mm 2 16 3 8 016B 1 2 0...

Страница 7: ...4 20mA P L 1 2 3 4 5 F mA flow F P flow T mA temperature 18 28VDC No display 1 2 3 4 5 brown black blue white grey brown black blue white grey Power supply Temperature analog Power supply Flow pulse...

Страница 8: ...eed the maximum pressure Pmax see type label Install switches only when power is off electrical hydraulic pneumatic danger Vibration and violent vibration must be avoided during transportation Even if...

Страница 9: ...be damaged If assembled without a specified tightening torque it may loosen the joint thread Installation of piping Please do not let the sealing tape into the tube Piping connection Please do not re...

Страница 10: ...mm 15DN 5DN Sensor upstream pipeline type Length of front and rear straight pipe section Concentric contraction Fully open valve A 90 degree bend Two on the same plane A 90 degree bend 20DN 5DN 25DN...

Страница 11: ...Two different planes A 90 degree bend Concentric expansion Regulating valve Half open Valve not recommended 40DN 5DN 30DN 5DN 50DN 5DN 10 www katusensor com...

Страница 12: ...may be damaged by something sharp and hard caution 0001 Level 1 M enu unit set M odified unit L m in m h m s cear volum e Clear cum ulative value K1 contronl channel M odify K1 control channel Flow t...

Страница 13: ...splay menu Flow L min TEMP 30 8 0 0 0 0 0 1 unit set L min In the parameter display state press Key to enter the setting state Just press the Add button Modify channel 0001 clear volume 0 000 m3 Click...

Страница 14: ...ure Change K1 control channel Flow and temperature K1 SET 0 0 Click the Add key or Decrease key Set K1 alarm value Set K1 alarm value K1 RESET 0 0 Click the Add key or Decrease key Set K1 reset value...

Страница 15: ...K2 control channel Flow and temperature K2 SET 0 0 Click the Add key or Decrease key Set the K2 alarm value K2 RESET 0 0 Click the Add key or Decrease key Set the K2 reset value K2 NO NC NC Click Add...

Страница 16: ...Flow L min TEMP 30 8 0 0 Switch set value the setting low clearance 0 0 L min Click Add key or decrease key Clear the low traffic value END 15 www katusensor com...

Страница 17: ...at the surface of the shell may become very hot if the operating temperature is higher warning Use of improper cleaning agent may damage the switch The following cleaning agents can be used to clean p...