User’s Manual
Kara BACnet Gateway
Page 23
Optionally:
•
BIBB - Device Management-Virtual Terminal-B (DM-VT-B)
The device supports following Object Types:
•
Device
•
Analog Inputs
•
Notification Class
6.1 BACnet Object Name
The BACnet Analog Object createt will get a default name as below:
Object Name:
XX_YYYYYYYY_ZZ
Where:
XX
is the Meter primary Address
YYYYYYYY
is the Meter Identification number
ZZ
is the record number
9.1 6.2 BACnet Services Supported
The M-Bus:BACnet Gateway supports following Services:
•
Read Property Service
•
Read Property Multiple Service
•
Write Property Service (support for priorities)
•
TimeSynchronization Service
•
UTCTimeSynchronization Service
•
Subscribe-COV Service
•
ConfirmedEventNotification Service
•
Subscribe-COV-Property Service
•
Who-Is and I-Am Services
•
Who-Has and I-Have Services
•
Create Object (for Notification Class Object)