background image

 

Tel.: 1 (450) 444 2030 

 Toll Free: 1-888-222-1560 

 Fax: 1 (450) 444 2029 

 InternetDN1781-1112 

  

Copyright © 2008 Tyco International Ltd. and its Respective Companies. All Rights Reserved. 

 Specifications may change without notice. 

Kantech and the Kantech logo are trademarks of Tyco International Ltd. and its Respective Companies. 

KT-MOD-OUT16  

KT-400 Expansion Module 16-Output with SPI Cable Install Sheet 

 

1. 

Introduction 

The 

KT-MOD-OUT16

 is a 16 zones output module. It can be 

used for elevator access control (may require additional 

hardware).  

The module supports daisy chaining; you can interconnect up to 

16 KT-MOD-OUT16 modules for a total of 256 external outputs 

per KT-400. You can mix relays and outputs in the same SPI 

group, up to 256 outputs. 

Note 1: The KT-400 SPI port maximum current draw, when the 

12V AUX terminals are not used, is 500 mA. 

Note 2: External power supply (12 VDC, 2 Amps) is required 

when the total current draw exceeds 500mA on the SPI Port. 

Note 3: There are already 4 relays available on the KT-400. 

Make sure to check the relays number assignments to prevent 

redundancy unless it has been planned on purpose. 

2. 

Specifications 

 

Maximum Current draw: up to 750 mA per module 

 

Connects to the KT-400 via the 6-pin SPI connector 

 

16 outputs low current module, 5 to 24 VDC, 4 to 750 mA 

 

Can be used for elevator access control or general output 

 

Can be mixed with output module KT-MOD-REL8 in the 
same SPI group 

 

Operating Temperature: -10C to +55C 

 

Maximum Humidity: 93% 

 

IP Class 3X,IK Rating 04,(when mounted in Kantech cabinet) 

3. 

Installing the KT-MOD-OUT16 

3.1. Unpacking 

The 

KT-MOD-OUT16

 package includes the following parts: 

 

One (1) KT-MOD-OUT16 module, 14 cm x 8 cm (5.7 in x 
3.25 in) 

 

 

One (1) SPI cable with 1 SPI connector, 41 cm (16 in) 

 

Four (4) plastic standoffs 

 

Two (2) installation sheets, English and French 

3.2.  Mounting 

The 

KT-MOD-OUT16

 can be installed inside a compatible cabinet 

(KT-MOD-CAB or KT-400) or mounted in a dry and secure 

location at less than 1 m (3 ft) from the KT-400. 

Perform the following steps to mount the unit: 

1. 

Press the four (4) plastic standoffs through the mounting 

holes of the cabinet,  

2. 

Secure the cabinet to the wall in the desired location. Use 

appropriate wall anchors when securing the cabinet to 

drywall, plaster, concrete, brick or other surfaces, 

3. 

Press the module into the plastic standoffs to secure the 

module to the cabinet. 

Once the unit is mounted, wiring may be started. 

3.3. Installation and Wiring 

Before beginning to wire the unit, ensure that all power (AC 

transformer and battery) is disconnected from the KT-400. 

Perform the following steps to complete wiring: 

1. 

Connect the 6-pin SPI connector to: 

 

the KT-400 SPI port, or 

 

the SPI OUT of the previous output module (

KT-MOD-

REL8

 and 

KT-MOD-OUT16 only

), or 

 

the SPI EXP of the 1st  input module 

KT-MOD-INP16 

connected to the KT-400 SPI port. 

2. 

Connect the six SPI wires (blue (BLU), white (WHT), green 

(GRN), yellow (YEL), black (BLK) and red (RED))  to the  SPI 

IN (TB1) terminals. 

3. 

Connect the 6-pin SPI connector from the SPI OUT to the 

next output module (

KT-MOD-REL8

  and 

KT-MOD-OUT16

 

only

). 

4. 

Complete all output wiring. 

 