background image

K T - 1 0 0   I n s t a l l a t i o n   M a n u a l

11

KT-100 Controller Maintenance 

To ensure the best operating conditions, it is highly 
recommended to test the KT-100 controller by performing the 
following tests.

Bi-annual test for battery

This test will ensure that if a power failure occurs, the battery 
will be able to support normal operations. This test should be 
performed twice a year.

1.

Remove AC power from the power supply and power 
the controller using the battery for one hour.

2.

Once the test has been performed successfully, 
reconnect the AC power to the power supply. No low 
power or power failure events should be reported to the 
system workstation.

Annual test for emergency lithium battery

Measure voltage of lithium battery when power is totally 
removed from the controller (AC & DC power). To ensure 
maximum operation and prevent loss of power, if the lithium 
battery voltage measures below 2.5 VDC, please contact your 
distributor to return the KT-100 for maintenance. 

Mounting the KT-PC4204

The KT-PC4204 package should include the following items:

One KT-PC4204 circuit board,

One ground wire assembly,

Five plastic standoffs,

One 5 A replacement fuse.

The KT-PC4204 should be located inside a compatible cabinet 
(Kantech part no. KT-4051CAB), mounted on a dry, secure 
location. Preferably, it should be placed at a convenient distance 
from the connected devices.

To mount and connect the power supply:

1.

Press the five plastic stands offs through the mounting 
holes at back of the cabinet.

2.

Secure the cabinet to the wall in the desired location. 
Use appropriate wall anchors when securing the cabinet 
to dry wall, plaster, concrete, brick or other surfaces.

3.

Press the circuit board into the plastic stands offs to 
secure the module to the cabinet.

4.

Mount the power supply unit.

5.

Install 120 / 230VAC / 16VAC, 40VA, class 2 wire-in or 
plug-in transformer.

6.

Place battery in the cabinet. If the AC supply is removed 
form the PC4204, the backup 12volt battery (if fully 
charged) will support normal operation for up to 12 
hours. An internal battery verification will cut the output 
power if the battery voltage level falls below 9.5 V DC.

7.

Connect the AWG#18 grounding wire to EGND

NOTE: 

Since the KT-100 uses high performance communica-

tions, proper grounding must be provided to ensure proper oper-
ation. An AWG#18 single conductor solid copper wire must be
used to ground each KT-PC4204 power supply to a good earth
ground as per the local electrical code (be careful of ground
loops). The ground clamp should be located below any other
ground. 

4 Relays Module PC4204

Input: 120 or 230 VAC
 Output: 16VAC/40VA

CLASS 2 (WIRE-IN)

To the KT100 controllers

(1.5 amps max.)

NUT

WASHER
CASE

SCREW

EARTH GROUND

PLUG-IN ALSO AVAILABLE
DO NOT CONNECT TO
RECEPTACLE CONTROLLED 
BY A SWITCH

SEALED ACID-LEAD
12 V BATTERY
7A/H MAXIMUM

KANTECH # KT-BD7-12

Jumper

Содержание kt-100

Страница 1: ... regarding product use and function and information on the limitations as to liability of the manufacturer The entire manual should be carefully read KT 100 Door Controller Installation Manual Kantech Systems Access Control and Accessories DN5073 0205 0207 ...

Страница 2: ...owners No part of this publication may be reproduced in any form without permission from Kantech Systems Inc Kantech Systems Web Site www kantech com 2002 Kantech Systems All rights reserved Specifications may be modified without notice Trademarks of Kantech Systems ...

Страница 3: ...6 Hooking up Inputs 6 Step 7 Connecting Readers and Keypads 7 Step 8 Connecting Control Relay Outputs 7 Step 9 Connecting the Tamper Switch 7 Step 10 Connecting the KT 100 to the RS 485 Bus 8 Section 3 Appendix 9 Typical KT 100 Wiring Diagram 9 KT 100 Compliance Notices 10 Troubleshooting Communication Problems 10 KT 100 Controller Maintenance 11 Bi annual test for battery 11 Annual test for emerg...

Страница 4: ...6 ...

Страница 5: ...in addition to presenting a valid card at the door reader For details about using the KT 100 Controller to interface another alarm panel refer to Using the KT 100 with an external alarm panel on page 12 Technical Specifications Input power 9 5 to 14 VDC 50mA accessories Max 750 mA Dimensions H W D 11 4 cm x 7 0 cm x 3 cm 4 5 2 75 1 25 mounted in a standard single gang electri cal box without any a...

Страница 6: ...4 K T 1 0 0 I n s t a l l a t i o n M a n u a l ...

Страница 7: ...ment or lines and at a minimum of 8 meters 25 feet from any transmitting equipment The controller should be mounted indoors in a secure location providing normal temperature and humidity levels Controllers should be located close to the controlled door Physical access using keys on controlled door must be provided so that the KT 100 can easily be accessed for servicing in case of malfunctions Step...

Страница 8: ...t can operate DC powered locking devices such as electromechanical strikes and can be configured to operate in fail safe or fail secure modes normal or reverse action The maximum permitted current is 250mA 12VDC per output NOTE Use 1K ohm end of line resistor between 12VDC and NC if not used This resistor is already included in the box KT 100 ACC To connect the door locking device 1 Connect the ne...

Страница 9: ... Connecting Control Relay Outputs The KT 100 provides two opto isolated contacts R1 2 and two control outputs R3 4 R1 2 can be used as either as dry contacts R1 R2 maximum voltage 30 volts AC DC maximum current 100 mA total R1 R2 R3 R4 maximum voltage 12 volts DC maximum current each relay 25 mA NOTE Use a KT RM1 optional to switch larger currents or voltages or to supply a dry contact Step 9 Conn...

Страница 10: ... 5 NOTE Intermittent communication problems or erratic opera tion may require to slow down the network speed to 9 600 or 19 200 baud Varying the network speed does not perceptibly change the operation speed of the system Usually most instal lations should be set at 19 200 baud To link KT 100 Door Controllers 1 Connect the RS 485 cable to X1 X1 and GND If you are not using the USB 485 or VC 485 con...

Страница 11: ...K Optional Exit Reader Door Locking Device 12 Volts DC 250 mA MAX Electrical Mag Lock 12 Volts DC 250 mA MAX IF NOT USED CONNECT A 1000 OHMS RESISTOR BETWEEN NC AND 12V IOProx Card Reader Entry Reader Door Contact WASHER Sealed Acid Lead 12 Volts Battery 7 A h Maximum KANTECH KT BD7 12 120 220 VOLTS 40VA CLASS 2 WIRE IN Plug in also available Do not connect to receptacle controlled by a switch EAR...

Страница 12: ...tion is done at Kantech The following steps should only be done if You changed the software e g you were using WinPass then installed EntraPass and there is no communication You replaced an existing KT 100 by another one on a loop To enable the default initialization hard reset 1 Disconnect the transformer and the battery from the PC4204 power supply 2 Remove all connections of Z1 DOOR and R3 term...

Страница 13: ...t a convenient distance from the connected devices To mount and connect the power supply 1 Press the five plastic stands offs through the mounting holes at back of the cabinet 2 Secure the cabinet to the wall in the desired location Use appropriate wall anchors when securing the cabinet to dry wall plaster concrete brick or other surfaces 3 Press the circuit board into the plastic stands offs to s...

Страница 14: ...sarm request of the third party alarm system This output is pulsed once to arm or disarm the alarm system according to the current arming state The KT 100 output Relay 4 in the example is connected to a local bell or to warn the alarm panel of an abnormal condition from the door Optionally one KT 100 input zone can be defined as an arming disarming request input for the external alarm panel In thi...

Страница 15: ......

Страница 16: ...Kantech Systems Web Site www kantech com 2002 Kantech Systems All rights reserved Specifications may be modified without notice Trademarks of Kantech Systems Printed in Canada DN5073 0205 0207 ...

Отзывы: