background image

DN1726-0811

18

Models Information

KT-400

: Cabinet with one KT-400 for North America, up to three expansion modules can be installed in the cabinet,

KT-400-PCB

: KT-400 with parts,

KT-400-ACC

: Accessory kit,

KT-400-CAB

: Cabinet only for North America,

 Table 2: Models Bills of Material

Note 1: 

The 

KT-400

KT-400-CAB 

models also include the KT-LOCK.

Note 2: 

The 

KT-400

KT-400-PCB 

models also include screws and locknuts.

Item Description

KT-400

(Notes 1,2)

KT-400-PCB

(Note 2)

KT-400-ACC

KT-400-CAB 

(Note 1)

KT-400 PCB

1

1

-

-

Cabinet

1

-

-

1

KT-400-ACC Accessory Kit

1

1

-

-

Ground wire (PCB to cabinet)

1

1

-

-

Ground wire (door to cabinet)

1

1

-

1

Tamper switch

1

-

-

-

Battery cable

1

-

-

-

Resistor 5.6K, 0.5W

-

-

32

-

Resistor 1K, 0.5W

-

-

4

-

Inner door sticker for North America, 

DN1762, 

Figure 14

1

-

-

1

Installation Manual DN1725 - French

1

1

-

-

Installation Manual DN1726 - English

1

1

-

-

Содержание Ethernet Four-Door Controller KT-400

Страница 1: ...DN1726 0811 KT 400 Ethernet Four Door Controller Installation Manual ...

Страница 2: ......

Страница 3: ...rical Specifications 16 KT 400 Ethernet Four Door Controller Models Expansion Modules Models 16 Models Information 18 Installing the KT 400 Ethernet Four Door Controller 19 Preparing to Install the KT 400 Ethernet Four Door Controller 19 Physical Installation 19 Earth Grounding 19 Door Locking Devices 19 Hooking Up Inputs 20 Connect readers and keypads 20 Relay Controlled Outputs 21 Auxiliary Outp...

Страница 4: ...DN1726 0811 iv Configuring the KT 400 Ethernet Four Door Controller with the KT Finder 33 Installation Checklist 37 Inputs and Outputs Assignments Sheet 38 ...

Страница 5: ...r the local authorities rules and regulations In the UK as per BS6701 An appropriate disconnect device must be provided as part of the building installation Where it is not possible to rely on the identification of the NEUTRAL in the AC MAINS SUPPLY the disconnecting device must disconnect both poles simultaneously LINE and NEUTRAL 2 AVOID setting up the equipment near heaters air conditioners ven...

Страница 6: ...00 Argentina Direct 5411 4717 2929 Direct 5411 4717 1320 Direct 5411 4717 5525 Fax 5411 4717 1060 9 00 to 18 00 ingenieria tycoint com Asia GMT 08 00 Singapore Direct 65 6319 9820 Fax 65 6319 9821 Direct 65 6389 8297 Fax 65 6389 8292 8 30 to 18 00 swhuin tycoint com wtooh tycoint com Europe Toll Free 800 CALL TYCO 800 2255 8926 GMT 01 00 Bahrain 800 04127 8 00 to 18 00 tfsemea support tycoint com ...

Страница 7: ...nectivity Only for supplementary use when planning to install the KT 400 Ethernet Four Door Controller with a UL 294 access control system Use only UL 294 or UL 1076 listed power supply Connect Kantech part number KT ACPW LED status indicator to the 16 VAC black terminals of the KT 400 Use Kantech part number KT BATT 12 battery see Note Note Backup battery provides operation of up to 12 hours but ...

Страница 8: ... supplied by an engine driven generator alone A standby battery is not required to be used A marking to identify the application and signaling function of the product is located on the inside of the unit inner door sticker For certified commercial proprietary control unit accessory applications the requirements of UL 1076 Commercial Proprietary Control Unit Accessory also apply Use Kantech part nu...

Страница 9: ...ith the KT Finder on page 33 for further details Four Onboard doors The KT 400 Ethernet Four Door Controller is a full 4 onboard doors access controller See Figure 1 for a description of the PCB and Figure 2 for all the connection possibilities offered by the KT 400 Ethernet Four Door Controller Communication Ports 1 10 100Base T Ethernet for network connection with the EntraPass Gateway 1 RS 232 ...

Страница 10: ... state Arming Disarming Request Postpone Arming Request Tamper switch input The tamper switch is a non programmable Fixed Function input It is used to identify tampering of the KT 400 cabinet Lock Outputs There are 4 onboard lock outputs and they are supervised The locking function can also be performed by any onboard relay configured for this functionality Relay Outputs There are 4 onboard relay ...

Страница 11: ...rns on each time the corresponding relay is activated AC PWR and DC PWR GREEN Theses LEDs are on when AC and DC power are present at the AC and or DC power input terminals ETH1 LINK GREEN The LED is OFF when there is no Ethernet network or the cable is disconnected and ON when there is an Ethernet cable and network connection ETH1 TXRX YELLOW The LED indicates network activity Built in SPI Expansi...

Страница 12: ...DN1726 0811 8 Figure 1 KT 400 Ethernet Four Door Controller PCB View ...

Страница 13: ...ESS CONTROL AND INTEGRATED SYSTEMS KT 300 KT 400 USB 485 0506 12V COM2 RX RS232 RX INPUT DOOR 3 COPYRIGHT C 2007 TYCO INTERNATIONAL LTD RELAY4 RED EGND GND 5V LK4 LK2 LK1 BUZ GND 4 GND LK3 LOCK VIN C TAMP NC RS 232 ETHERNET 1 3 C NC NO C NC NO RELAY 2 1 C C NC NO NC NO RELAY COM2 485 AUX BUZ 12V D1 5V D0 GND GRN YEL READER DOOR 2 RED BUZ D1 5V D0 GRN YEL READER DOOR 3 RED BUZ 12V D1 D0 GRN YEL REA...

Страница 14: ...DN1726 0811 10 Figure 3 KT 400 Cabinet Model for North America ...

Страница 15: ... Corporate Gateway Over the internet See Figure 4 Over RS 232 with a USB 485 See Figure 5 Application with EntraPass Global Edition and a Global Gateway Over RS 232 with a VC 485 See Figure 6 Application with EntraPass Global Edition and a KT NCC Over the internet with a KT NCC See Figure 7 Application with EntraPass Special Edition Corporate Edition and Global Edition Over RS 232 straight from En...

Страница 16: ...DN1726 0811 12 Figure 5 USB 485 with EntraPass Special Edition and Corporate Edition with Corporate Gateway Figure 6 VC 485 with EntraPass Global Edition and Global or Corporate Gateway ...

Страница 17: ...1726 0811 13 KT 400 Ethernet Four Door Controller Installation Manual Figure 7 Over the internet with a KT NCC and EntraPass Global Edition Figure 8 Over RS 232 straight from the EntraPass RS 232 COM port ...

Страница 18: ... if you must reset or change the communication mode of the KT 400 Ethernet Four Door Controller Table 1 VITAL LED Heartbeat Patterns Booting Up Steady Factory Default DHCP Continuous LONG Pulses Unable to Resolve DNS 2 LONG Pulses Forced Default Static 3 LONG Pulses DHCP Server Failed 4 LONG Pulses Receive Broadcast Single 2 5 Sec Burst Card Read or Swipe Single 0 5 sec burst resume previous flash...

Страница 19: ...switch input Points maximum wiring AWG 22 600 m 2 000 ft Door strike power 12 VDC 250 mA max for KT 400 supervised Reader outputs 16 outputs 25mA max each open collector outputs Auxiliary outputs LEDs LED OUT1 and OUT2 and buzzer Buz for each individual door 25mA max each open collector outputs Relay controlled output 4 onboard Form C Relay controlled outputs 30 VDC 3 Amps max each Communication p...

Страница 20: ...0 PCB KT 400 Ethernet Four Door Controller PCB only IP Ready with Accessory Kit see Table 2 KT 400 CAB KT 400 Black Metal Cabinet with Lock and Keys see Table 2 Expansion Modules Models KT MOD INP16 KT 400 Expansion Module 16 Zone Inputs with SPI Cable 41 cm 16 in KT MOD REL8 KT 400 Expansion Module 8 Relay with SPI Cable 41 cm 16 in KT MOD OUT16 KT 400 Expansion Module 16 Output with SPI Cable 41...

Страница 21: ...lish version Dimensions Drawings DN1846 KT 400 PCB Dimensions Drawing in DWG Format DN1847 KT 400 PCB Dimensions Drawing in PDF Format DN1848 KT 400 CAB Dimensions Drawing in DWG Format DN1849 KT 400 CAB Dimensions Drawing in PDF Format Miscellaneous Items CBLK 10 Cable kit RS 232 cable 30 m 100 ft with RJ 12 connectors for PC to master KT 400 740 1023 DB9F to RJ 12 adaptor and 740 1041 DB9M to DB...

Страница 22: ...els also include the KT LOCK Note 2 The KT 400 KT 400 PCB models also include screws and locknuts Item Description KT 400 Notes 1 2 KT 400 PCB Note 2 KT 400 ACC KT 400 CAB Note 1 KT 400 PCB 1 1 Cabinet 1 1 KT 400 ACC Accessory Kit 1 1 Ground wire PCB to cabinet 1 1 Ground wire door to cabinet 1 1 1 Tamper switch 1 Battery cable 1 Resistor 5 6K 0 5W 32 Resistor 1K 0 5W 4 Inner door sticker for Nort...

Страница 23: ...terference at a minimum distance of 1 m 3 ft from telephone equipment or lines and at a minimum of 8 m 25 ft from any transmitting equipment Physical access using keys on controlled doors must be provided so that the KT 400 Ethernet Four Door Controller can easily be accessed for servicing in case of malfunction Earth Grounding AWG 18 grounding wire to EGND Since the KT 400 Ethernet Four Door Cont...

Страница 24: ...erved for the second controlled door The contact is assigned input 5 and the associated request to exit detector as input 6 Inputs 9 and 10 are automatically reserved for the third controlled door Inputs 13 and 14 are automatically reserved for the fourth controlled door There is no obligation to follow these rules but this standard convention facilitates servicing Connect readers and keypads READ...

Страница 25: ...xpansion Port on page 24 for additional details concerning the external power supply requirement for expansion modules Auxiliary Outputs Connect auxiliary outputs to readers and local warning devices Auxiliary outputs are used for visual and audible signal They can be activated according to input conditions or events and local alarms Auxiliary outputs READER DOOR 1 to 4 LED provide visual feedback...

Страница 26: ...splitters or spider web star networks Note 3 If the 12 VDC is already used the RS 485 signal ground can be connected to the other GND terminals on the KT 400 The EGND earth ground terminal cant be used for signal ground only use the GND and 12 VDC negative terminals for signal ground Note 4 There is no end of line resistor to install on the RS 485 COM1 terminals on the last KT 400 controller of a ...

Страница 27: ...iring for data exchange between EntraPass and the controllers Powering the KT 400 Ethernet Four Door Controller Install 120 VAC IN 16 VAC 75 VA OUT class 2 transformer Place battery in cabinet Power up the KT 400 Ethernet Four Door Controller The KT 400 must be powered by a 16 VAC 75 VA class 2 wire in or plug in transformer After you have completed all the necessary steps you can power up the KT ...

Страница 28: ...he SPI chain current draw Example of current draw calculation 1 15 modules KT MOD OUT16 x 750 mA 11250 mA 2 11250 mA 500 mA or 0 mA if the 12 VDC AUX of the KT 400 is used 10750 mA 3 10750 mA divided by 1850 mA 5 8 which means in fact 6 external power supplies 12 VDC 2 Amps are required 4 Connect an external power supply at every expansion module where the current draw has reached 1 85 Amps 5 Make...

Страница 29: ... Don t forget to check the relays number assignments to prevent redundancy unless it has been planned on purpose For more details concerning the expansion modules refer to the following documents Part number Description DN1775 KT MOD INP16 Install Sheet French version DN1776 KT MOD INP16 Install Sheet English version DN1780 KT MOD OUT16 Install Sheet French version DN1781 KT MOD OUT16 Install Shee...

Страница 30: ...DN1726 0811 26 Figure 10 PCB View of Expansion Modules ...

Страница 31: ... INTERNAL or EXTERNAL SUPPLY 12 VDC up to 750 mA O2 SPI IN YEL RED WHT BLU BLK GRN Pos LED Neg O1 O11 24VDC O12 O16 O14 O13 O15 EXT INT PWR O10 Pos Neg OUTPUT DEVICE 5 to 24 VDC up to 750 mA BUZZER Neg O4 O3 O8 O6 O5 O7 O9 PCA DC 12V G BK B W R Y DC 12V C 2007 08 0801 REV A 0 16 OUTPUTS SPI MODULE Z12 SPI IN EOL FAST NO NC SLOW DRY BLU VITAL C Z6 Z7 Z8 Z4 C Z2 Z3 C Z5 C Z10 C Z9 Z11 C Z1 YEL RED W...

Страница 32: ...DN1726 0811 28 Figure 12 Expansion Modules Cabinet for North America ...

Страница 33: ... Hard Reset When JP2 is OFF and JP3 is ON All controller s memory is settled to default values Internal event buffer is cleared IP address is kept if valid Controller generates the message Controller Hard Reset Internal RTC Real Time Clock and clock are settled to the default time and date values January 1st 2005 00 00 00 Saturday 3 long pulses Forced Default Static When JP2 is ON and JP3 is OFF S...

Страница 34: ... another site and there is no communication How to reset the KT 400 Ethernet Four Door Controller for Factory Default DHCP mode Before you start Locate the reset button the two jumpers JP2 JP3 and the blue VITAL LED The Ethernet cable must be connected to the corporate network The green LINK LED should lit and the yellow TXRX LED should be flashing The blue VITAL LED should be flashing 1 Remove JP...

Страница 35: ... the batteries Do not apply pressure to or deform the batteries Ensure that the above precautions are strictly observed by related departments including but not limited to production sales and outside contractors Regarding the recommended battery 12 VDC 7 Ah It is the end user and or installer responsibility to assure that the disposal of used batteries is made according to the waste recovery and ...

Страница 36: ...appropriate network cable that you need 1 Make sure the KT 400 is in Forced Default Static mode before starting the configuration Verify the heartbeat patterns to determine the status See Table 3 on page 29 for details 2 Start your web browser and enter the following IP 192 168 1 2 and press Enter 3 Put a jumper on JP3 Both jumpers should now be on JP2 and JP3 4 Enter the IP addresses as per the N...

Страница 37: ...ion is C Program Files Kantech Server_xE Bin or on the EntraPass CD ROM or available as a free download from http www kantech com 1 Quit all EntraPass applications 2 Make sure the KT 400 is in Factory Default DHCP mode See Table 3 on page 29 3 Start the KT Finder Note If you try to run the KT Finder while running EntraPass you will get an error message similar to this 4 Select KT 400 from the Devi...

Страница 38: ...y This information must be the same as entered in EntraPass workstation for Devices Site Select Obtain an IP address automatically or Use the following IP address This information must be the same as entered in EntraPass workstation for Devices Site 9 Change the Port number if required Note The port number should only be changed when you have more than one KT 400 at the same remote site 10 Click O...

Страница 39: ...N or WAN see other side Configuration in a Local Area Network LAN For more details refer to the EntraPass Reference Manual MAC Address 00 50 F9 ______ ______ ______ Port 18810 by Default or _________ IP Address Type DHCP or Static IP Address ______ ______ ______ ______ Subnet Mask ______ ______ ______ ______ Default Gateway Router ______ ______ ______ ______ EntraPass Special Edition Corporate Gat...

Страница 40: ...18001 UDP and 18801 UDP KT 400 Ethernet Four Door Controller Site MAC Address 00 50 F9 ______ ______ ______ IP Address Type Static or Reserved DHCP IP Address ______ ______ ______ ______ Subnet Mask ______ ______ ______ ______ Default Gateway Router ______ ______ ______ ______ DNS Server IP Address ______ ______ ______ ______ Router Public IP Address ______ ______ ______ ______ or Domain name ____...

Страница 41: ... to 16 Resistors for all inputs 5 6K ohm if necessary Connect readers and keypads Auxiliary Outputs Connect auxiliary outputs to readers and local warning devices Tamper Protection Install tamper switch on cabinet Connecting the KT 400 Ethernet Four Door Controller Connecting the VC 485 or the USB 485 to the RS 485 Bus Connect the RS 485 cable to COM1 485 and the RS 485 signal ground to the 12 VDC...

Страница 42: ...DOOR Z5 NO or NC EOL DRY or DEOL REX Z6 NO or NC EOL DRY or DEOL INPUT Z7 NO or NC EOL DRY or DEOL INPUT Z8 NO or NC EOL DRY or DEOL DOOR Z9 NO or NC EOL DRY or DEOL REX Z10 NO or NC EOL DRY or DEOL INPUT Z11 NO or NC EOL DRY or DEOL INPUT Z12 NO or NC EOL DRY or DEOL DOOR Z13 NO or NC EOL DRY or DEOL REX Z14 NO or NC EOL DRY or DEOL INPUT Z15 NO or NC EOL DRY or DEOL INPUT Z16 NO or NC EOL DRY or...

Страница 43: ...DN1726 0811 39 KT 400 Ethernet Four Door Controller Installation Manual Figure 14 KT 400 Cabinet Inner Door Sticker Diagram North America Figure 15 ...

Страница 44: ...DN1726 0811 40 ...

Отзывы: