CONNECTION 

 

602 

 

652 

 

 
 

 

 

ASSEMBLY AND COMMISSIONING 

 

 

Turn the pressure switch with its mounting thread (1) into the intended pressure connection (observe maximum tightening torque). Use a 
suitable sealing ring for sealing. 

 

 

With device connector 600/601: 
Remove the device connector before adjusting the pressure switch. 

 

 

 

Connect the electrical connections (2) to a continuity tester. 

 

Completely screw in the adjusting screw (3) with low torque. Then unscrew the adjusting screw until the continuity tester reacts and set 
the desired switching pressure. Never unscrew the adjusting screw completely. 

 

When commissioning the pressure switch, please observe the relevant safety regulations of the employers' liability insurance association or the 
relevant national regulations. 

 

 

 

DISASSEMBLY 

 

Observe the following instructions when removing the pressure switch: 

 

The pressure switch must be in a depressurized and de-energized state. 

 

Remove the pressure switch using suitable tools on the provided key surfaces or hexagonal profiles. 
If other surfaces or unsuitable tools are used, damage may occur. 

 

Observe all relevant safety regulations. 

 

 

 

NOTE 

 

The data and descriptions in this manual have been compiled to the best of our knowledge and belief. However, the manufacturer cannot be held 
liable for any errors. In any case, the operator must ensure that a failure or defect in the product cannot lead to further damage. Furthermore, 
This translation has been created to the best of our knowledge. If any doubt arises, the original version in German uploaded on our homepage 
must be applied. 

 

Caution: Only tighten the pressure switch on the metal housing 

 danger of damage! 

 

Caution: Observe the permissible electrical switching capacity 

 danger of damage! 