5.Error and Troubleshooting
No.
Symptom
Possible causes
Corrective action
1 Controller start failure
Power connect failure
Check the power source and connecting wire
Internal circuit problem
Connect with manufacturer
2 Fan motor will not run
Power phase shortage
Check the power supply
Motor controller line is not
connected or poor connect.
Check the Motor Control line on the back of
Controller
Motor controller failure
Restart Controller. Or connect with manufacturer
3 Touch screen failure
External disturbances
Check around, away from the possible
external disturbances, re-start the Controller.
Capacitive touch screen only
recognizesa fingertouch
Finger touch directly
Touch screen failure
Connect with manufacturer
4
Temperature display
wrong
Temperature line is not connected
or poor connect.
Check and well connect the temperature line.
5
Air flow range displayed
wrong
Testing tool set wrong matching with
the fixed one.
Re-set the testing tool or re-install the matching
testing tool.
6 USB data exporting failure
USB disk failure.
The available USB disk should be: support USB2.0
protocoland FAT file format.
After plug-in USB disk, data
exporting available only once.
USB disk unplug then back plug in for data
exporting again.