Notes for installation
Noise
Electric wiring
Install in a location where is firm enough to avoid the enlargement of noise
and vibration.
Don’t put anything in front of the outlet of the unit to avoid increasing
noise.
Be sure that hot air or noise will not inconvenience neighbors.
Please contact the seller as soon as there is strange noise during operation.
Please use the safety support.
Must connect with ground reliably.
The exclusive circuit must be used. But removable socket can’t be used because poor
contact of it can cause over heat or fire.
If the supply cord is damaged, it must be replaced by the manufacturer or your dealer
In fixed circuit, there must be electricity leakage protection switch and leakage current
is less than 30mA.
Air switch (thermal-magnetic breaker) should be installed in the circuit
.
Don’t pull the power cord strongly.
or a qualified person to avoid a hazard.
All The dectrical work must be done according to the local wiring regulations.
Connecting method between air conditioners and power cord and interconnecting method
of each individual element with one another should accord with wiring diagram on the unit.
The air conditioner should be installed in accordance with national wiring regulation.
An all-pole disconnection switch having a contact separation of at least 3mm in all poles
should be connected in fixed wiring
- 6 -
Shall be installed in the cirrcuit of miniature circuit switch and it has a capacity of 10A (
KA-W072M
,
KA-W092M
,
KA-W122M
), 16A (
KA-W182M
) or 25A (
KA-W242M
).
Fixed line shall be greater than 1.5mm (
KA-W072M
,
KA-W092M
,
KA-W122M
), and 2.5mm
(
KA-W182M
,
KA-W242M
);