KANE450
manual
Page
19
MEASURING PRESSURE
The analyser can be used to measure pressure by connecting tubing to the appropriate ports.
Standard Pressure Report ....
this mode is accessed via the MENU function
This mode allows a tightness test to be carried out automatically.
The times for the test can be set by the user.
From the start of the test the analyser waits 60 secs to allow temperature stabilisation, then
records and displays the pressure reading at the start of a 120 second countdown. The live
pressure reading is displayed during the 120 second countdown and then locked at the end of
the countdown. The display then shows start pressure and finish pressure. The summary
results can then be printed as below:
Pressure Test Printout
K450
1.0
Serial No.
123456789
[email protected]
KANE INTERNATIONAL
..............................................
Tightness Test
..............................................
LOG
03
TIME 14:58 12/12/05
PRS_1
mbar 20.110
PRS_2
mbar 19.998
Duration
mins 2:00
................................................
customer
................................................
appliance
.................................................
Ref:
..................................................