Type 66-0F-000-100
1. General information
The LON module for MULTICAL
®
makes it possible to integrate the MULTICAL
®
heat meter in a LON
network via the module's FTT-10 A transciever. This ensures an ideal data transfer to the CTS system, as
the remote registration always corresponds with the local reading.
When the LON module is used together with MULTICAL
®
type 66-CDE, type 66-MP type 66-ST or
MULTICAL
®
III type 66-B the actual data for water flow, temperature and power is updated every 60 sec..
Furthermore, a program version with more frequent up-dates is available. Current flow, temperature and
power data is updated every 10 seconds, which means that current heat meter data can be used as
input veriables for regulation. Other data is updated at intervals of 50 secons. This program version is
available at Kamstrups home page. (
www.kamstrup.dk
).
Temperature records and power calculation are updated for every energy integration in MULTICAL
®
(20…600 sec. interval depending on the actual water flow).
Kamstrup makes a complete functional test at the factory, therefore the module is delivered
Configured. Which is why the service LED will be off when voltage is supplied.
Please refer to the EcheLon Engineering Bulletin ”LonWorks Custom Node Development”, which
explains the various indications of the "Service" LED.