The UDP port can also be customized and can be any round number in the range of 47808 – 47823.
It is recommended that the UDP port stays unchanged, since the default value is widely used.
Please consult with your BMS admin before changing the UDP port.
D. Restarting the service
On the Settings –> Device Details –> Connectivity –> BACnet/IP screen, there is a Restart Service button.
Please use this button when you need to restart the BACnet service during setup.
3.
Setting up network connection on Sensedge
BACnet/IP requires a connection to the local network for data transmission. This connection can be
achieved by having your Sensedge connected via Ethernet or Wi-Fi to your local network.
A. Setting up your Wi-Fi connection on the Sensedge
On the Settings –> Wi-Fi screen, you can select the SSID for the Sensedge to connect to.
The Sensedge supports 2.4GHz Wi-Fi, 802.11b/g/n. And, for security, it supports the latest 64/128 WEP,
WPA-PSK, WPA2-PSK, WPA, WPA2. It also supports 2-step verification via CaptivePortal.
Internal PKI (Public Key Infrastructure) is NOT supported.
On the Settings –> Wi-Fi –> IP address –> Configure screen, you can toggle between “Auto” and “Manual”
Connection Types. This setting regulates the method that your Sensedge uses to acquire its IP address,
Subnet Mask, and Gateway.
Please consult with your network admin if you have question regarding your local network.